NT support tool (V053-E1-1) (986753), страница 64
Текст из файла (страница 64)
32 groups in overlapping screen)Limits on Numbers of ElementsAppendix ENew ModelsItemLimitFixed Display65535 entries/screen (overlapping screen*1: max. 524280 entries)Numeral Display256 entries/screen (overlapping screen*1: max. 1024 entries)String Display256 entries/screen (overlapping screen*1: max. 1024 entries)Image Data256 entries/screen, including library data(overlapping screen*1: max. 1024 entries)Library Data256 entries/screen, including image data(overlapping screen*1: max. 1024 entries)Mark Display (fixed dis- 65535 entries/screen (overlapping screen*1: max.
52480 entries)play)Bar Graph50 entries/screen (overlapping screen*1: max. 400 entries)Analogue Meter*250 entries/screen (overlapping screen*1: max. 400 entries)Broken-line Graph1 frame/screen (overlapping screen*1: max. 8 frames) 256 lines/frameTrend Graph1 frame/screen (overlapping screen*1: max. 8 frames)Data logging function not used:50 lines/screen dataData logging function used:8 lines/screen dataLamp256 entries/screen (overlapping screen*1: max. 1024 entries)Touch Switch256 entries/screen (overlapping screen*1: max.
1024 entries)NumeralInputNumericKey Type256 entries/screen (overlapping screen*3: registration is possible only onone child screen)Thumbwheel SWTypeNT31/NT31C: 64 entries/screen (overlapping screen*4: registration ispossible only on one child screen.)NT631/NT631C: 256 entries/scren (overlapping screen*4: registration ispossible only on one child screen.)Data Input – String256 entries/screen(overlapping screen*3: registration is possible only on one child screen.)Alarm List4 groups/screen (max.
32 groups in overlapping screen*1)(Alarm history: One group each for occurrence order and frequency order in standard/child screen)Alarm History*1: Limits on numbers of elements on a window/keyboard screen is same as on astandard screen. Limit check is not performed for an overlapping screen at theSupport Tool.*2: Analogue meter can be used only with NT31, NT31C, NT631 and NT631C with“-V1”.*3: Either of numeral input (numeric key type) or string input can be registered on awindow/keyboard screen.*4: Thumbwheel type numeral input can not be registered on a window/keyboardscreen.523Limits on Numbers of ElementsAppendix ELimits on displayFor elements, limits are also applied to display in addition to the limits on the numbers shown above.
Limits on reading the dataFor NT31, NT31C, NT631, and NT631C, the allowable number of data entriesthat can be read at the same time is set and read elements exceeding this limitare not displayed. If the same data is read from different elements, reading of thedata is counted separately.The allowable maximum number of data entries that can be read is shown belowfor each type of data.524ItemMax. EntriesNumeral Memory Table1024 entriesString Memory Table1024 entriesBit Memory Table1024 entriesIndirect Memory Table Reference100 entriesLimits on Numbers of ElementsAppendix EThe read data count is indicated below for each element.Read Data CountElementFixed Display(characters, graphics)NoneImage DataNoneLibrary DataNoneMarkNoneTouch SwitchHost bit: 1LampHost bit: 1Data Input – NumeralNumeral memory table: 1Data Input – StringCharacter string memory table (String table): 1Thumbwheel SwitchNumeral memory table: 1Numeral DisplayDirect designationNumeral memory table: 1Indirect designationNumeral memory table: 1Memory table indirect reference: 1String DisplayDirect designationCharacter string memory table (String table): 1Indirect designationCharacter string memory table (String table): 1Memory table indirect reference: 1Bar GraphNumeral memory table: 1Note: If numeral memory tables are specified for 100% value, 0% valueand –100% value, a numeral memory table is readfor each of them.Analogue MeterNumeral memory table: 1Note: If numeral memory tables are specified for 100% value, 0% valueand –100% value, a numeral memory table is read for each ofthem.Broken-line GraphNumeral memory table: “Line No.” x “No.
of Points”Note: If numeral memory tables are specified for 100% value, 0% valueand –100% value for each line, a numeral memory table is readfor each of them.Trend GraphWithout data loggingfunctionNumeral memory table: “Line No.”With data loggingfunctionBackground table: “Line No.”Note: If numeral memory tables are specified for100% value, 0% value and –100% valuefor each line, a numeral memory table isread for each of them.Note: If numeral memory tables are specified for100% value, 0% value and –100% valuefor each line, a numeral memory table isread for each of them.Alarm ListBit memory table: “No. of Reference”Alarm HistoryNone525Appendix F New Functions of Support Tool Ver.3.2Appendix FAPPENDIX FNew Functions of Support Tool Ver.3.2Here, differences between the Support Tool Ver.3.0 and Ver.3.2 and the new functions added to Ver.3.2 are shown in the table.
Various functions are added toVer.3.2 to improve operational efficiency.ItemsNT31, NT31C, NT631,NT631C system program Ver.2.1 supportVer.3.0Not supportedVer.3.2The following functions are supported. Image/Library indirect referencePage6–2–96–2–116–3 Up to 65535 fixed display objectscan be registered for a library(With Ver.3.0, up to 64 objects canbe displayed). With NT631 and NT631C, up to40 characters can be displayed foralarm list/history message regardless of the display method.System is changed so that thescreen switching speed on PT is improved.526Importing screen ortable data from a different screen data fileNot possible (Only oneSupport Tool can bestarted up).Possible (Different screen data files 3–3–6can be opened by starting up twoSupport Tools to perform copy operation of screen/table data betweenSupport Tools.
Between the samePT model only).Property sheet opensautomatically whencreating objects.You need to display the Automatically displays the propertyproperty manually after setting dialog at the same time anregistering an object on object is registered on the screen.the screen.Object selection usingthe Tab key or Shift +Tab key.Not possible.Possible (object will be selected one 6–1–3by one according to the display order.
Pressing the Tab key selectsthe object according to the higherdisplay order. Pressing the Shift key+ Tab key selects the object according to the lower display order).Displaying the propertyby pressing the Alt key+ Enter keyNot possiblePossible (only when a single objectis selected).6–1–10Direct selection of anobject overlapped bythe other objects.Not possiblePossible (The element with thesmallest area enclosing the point ofselection is selected).6–1–3Alignment functionNoneObjects can be aligned by the alignment function. (from menu, toolbaror short–cut key).6–1–6Appendix F New Functions of Support Tool Ver.3.2ItemsVer.3.0Appendix FVer.3.2PageFilter functionNoneOnly the objects of the selected type 5–1–4is displayed by selecting the objecttype using a toolbar (Screen editingis also possible during the filter function.
This function is cancelled whenthe alignment function is used).Object information displayed on the statusbarNoneDetailed information of the selectedobject is displayed.3–2–1Information in the select object dialog boxOnly the object name is Detailed information of the selecteddisplayed.object is displayed.6–1–3Display of inverse, flash Can not display on the Inverse attribute is always shown.and inverse flash attrib- Support Tool (They are Flash attribute can be checked fromute of objectsdisplayed as “standard” a menu or a toolbar.attribute on the SupportTool).5–1–3Display of lamp ON sta- Not possibletus for lamps and touchswitches5–1–3Lamp ON status can be checkedfrom a menu or a toolbar.Show tag for a touchswitch with a notify bitfunctionOnly “notify bit” address Both “notify bit” address and “lampis displayed.bit” address are shown.5–1–3Handles displayed forobjectsGreen handle onlyAn arrow indicating the direction to6–1–4which the object can be resized isdisplayed inside the green handle (Ithelps to distinguish between thehandle and screen grid whenzoomed).Handle size whenzoomedHandle size is alsozoomed when usingzoom function.
It disturbs the operation witha small object.Handle size does not change evenwhen the zoom function is used(This enables the smooth edit operation).5–1–3Functions of image/library It takes time to display Image/librarytable. Image/library table is displayedquickly.8–18–2 Copy/paste operation is possible Copy/paste operationon the image/library editor.is not possible on the It is possible to select multipleimage/library editor.data on the image/library table It is not possible to(multiple image/library data can beselect multiple datadisplayed collectively).on the image/library Image/library data can be pretable (cannot displayviewed.multiple image/librarydata collectively).
Preview function ofimage/library data isnot supported.527Appendix F New Functions of Support Tool Ver.3.2ItemsMultiple displays ofimage/library editorVer.3.0Up to 1 editor can bedisplayed at the sametime.Ver.3.2PageUp to 10 editors can be opened collectively by selecting multiple codeson the image/library table (Theimage/library table closes at thesame time).8–18–2Modifying the size of an Not possibleimage data on theimage editorImage data size can be modified bydragging the handle ( mark) ofrange specifying frame.8–1–2Display method ofproperty for lamp/touchswitch labelOnly the text can beedited by clicking on[Edit Label] button inthe lamp/touch switchproperty.
You need toselect the label usingthe Edit Object functionto display a property.All the properties of label can be dis- 6–5played by clicking on [Edit] button in 6–8the lamp/touch switch property andthe settings such as scale or colorcan be changed in it. It is also possible to select the label directly byclicking it while pressing the Shiftkey and Ctrl key.Copying the I/O comment to lamp/touchswitch labelFirst, you need to display the I/O commenttable and then performcopy operation manually.[Copy I/O Comments] button is add- 6–5ed in the property dialog (For notify6–8bit touch switch, I/O comment ofnotify bit is copied and for touchswitch with other functions, I/O comment of lamp bit is copied).Centralization of lamp/touch switch labelYou need to adjust thelabel position manually.Label can be centralized horizontally 6–1–9by the [Centralize Label] function(from menu or toolbar).