NT support tool (V053-E1-1) (986753), страница 60
Текст из файла (страница 60)
It is discarded.Create a new numeralsetting input field (thumbwheel switch). Correctthe screen data or theprogram in the host sothat a constant of up to 8digits suffices. (Refer to6-4-1, 6-4-3.)Correction related the reference memory tables for numeral inputIn the conversion of the data between a conventional and a new model, conversionis executed in the manner shown below due to differences in the numeral memorytables which can be referred to. DifferenceNew models:For numeral memory tables No.
247 to No. 253, reference is not possible for numeral input/thumbwheelswitch.Conventional models:For numeral memory tables No. 247 to No. 253, reference is possible for numeral input/thumbwheel switch.(Display only) Conversion result, error message and corrective action486Status beforeConversionStatus afterConversionError MessageCorrective ActionWith a conventionalmodel, a numeralsetting input field (ora thumbwheelswitch) for which anumeral memorytable in the rangeNo. 247 to No.
253is referred to is registered to the symbolmanager.With a new model,the reference numeral memory tableNo. is corrected to“0”.Thumbwheel switchrefers to reservednumeral table entry.The referenced tableentry is reset to 0.Make corrections so thatthe contents of a numeralmemory table in therange No. 247 to No.
253are displayed in a numeral display. (Refer to 6-6.)Data ConversionAppendix ACorrection related the number of digits for numeral displayIn the conversion of the data between a conventional and a new model, conversionis executed in the manner shown below due to differences in the range of numericvalues which can be displayed. DifferenceNew models:A numeric value of up to 10 digits can be displayed.Conventional models:A numeric value of up to 8 digits can be displayed.
Conversion result, error message and corrective actionStatus beforeConversionStatus afterConversionError MessageCorrective ActionWith a new model, anumeral display element for which a numeric value exceeding 8 digits is displayed is registeredto the symbol manager.With a conventionalmodel, a numeraldisplay element ofgreater than 8 digitsis discarded.Numeral Display:Total number of integer and decimal exceeds limit. It is discarded.Create a new numeraldisplay element. Correctthe screen data or theprogram at the host sothat a constant of up to 8digits suffices.
(Refer to6-6.)Correction related to analogue meterIn the conversion of the data between new models (with “-V1”) and other PT models, conversion is executed in the manner shown below due to presence/absenceof analogue meter. DifferenceNew models (with “-V1”): Analogue meter can be used.Conventional models, new models (without “-V1”):Analogue meter cannot be used. Conversion result, error message and corrective actionStatus beforeConversionStatus afterConversionWith a new model(with “-V1”), an analogue meter is registered to the symbolmanager.With a conventionalmodel and a newmodel (without“-V1”), an analoguemeter is not displayed.Error MessageCannot paste analogue meter. It isdiscarded.Corrective ActionCreate a bar graph orother display elementinstead of an analoguemeter to display contentswhich was displayed byan analogue meter.487Data ConversionAppendix ACorrection related to control touch switch of trend graphIn the conversion of the data between a conventional and a new model, conversionis executed in the manner shown below due to differences in the trend graph control touch switches.
DifferenceNew models:Marks with codes FFEF to FFF5 (hexadecimal) areused as trend graph control touch switches.Conventional models:No trend graph control touch switches (codes FFEF toFFF5 may be used as desired). Conversion result, error message and corrective actionStatus beforeConversion488Status afterConversionError MessageCorrective ActionWith a conventionalmodel, the markswith codes FFEF toFFF5 are used asdesired.With a new model,marks registeredwith a conventionalmodel are used astrend graph controltouch switches.––(1) Copy marks registered under codesFFEF to FFF5 to other codes with themark editor.(2) Reset the marks withcodes FFEF to FFF5with the mark editor.(By resetting, themarks are returnedto the trend graphcontrol marks.)(3) For the elementswhich use the conventional marks ofcodes FFEF to FFF5,correct the codes tothose assigned aftercopying the marks.(Refer to 8-3.)With a conventionalmodel, the markswith codes FFEF toFFF5 are not used.With a new model,nothing is registeredfor codes FFEF toFFF5 and trendgraph control touchswitches are not displayed.––Reset the marks withcodes FFEF to FFF5 withthe mark editor.
Themarks of these codes arerecognized as the trendgraph control marks.(Refer to 8-3.)Data ConversionAppendix ACorrection related to sampling cycles of trend graphsIn the conversion of the data between a conventional and a new model, conversionis executed in the manner shown below due to differences of trend graph samplingcycles. DifferenceNew models:The sampling cycle can be set in the range from 0.5 to6553.5s in units of 0.5s.Conventional models:The sampling cycle can be set in the range from 0.1 to6553.5s in units of 0.1s. Conversion result, error message and corrective actionStatus beforeConversionStatus afterConversionWith a conventionalmodel, the samplingcycle is set in unitsother than 0.5s.With a new model,the sampling cycle iscorrected to 0.5sunit cycle (correctedto the nearest value).Error MessageCorrective Action[W]Sampling cycle lessthan minimum value.Minimum value restored.[W]Sampling cycle notmultiple of 5.
Valuerounded off to nearest multiple of 5.Since there are no problems in actual operation,correction is not necessary.Correction related to the 100% value, 0% value and –100% value of a graphIn the conversion of the data between a conventional and a new model, conversionis executed in the manner shown below due to differences in the range of numeralwhich can be input. DifferenceNew models:A numeric value of up to 10 digits can be input for a %value.Conventional models:A numeric value of up to 8 digits can be input for a %value. Conversion result, error message and corrective actionStatus beforeConversionStatus afterConversionWith a new model, agraph for which avalue greater than100000000 or smaller than –10000000is set for a % valueis registered.With a conventionalmodel, if a % valueis outside the allowable range, it is replaced as shown below: for a 100% value, the existing value is corrected to“100”, for a 0% value, it is corrected to“0”, and for a –100%value, it is correctedto “–100”.Error MessageCorrective Action[W][Object Name] – %value is out of limit.Default values restored for 100%, 0%and –100%.Correct the screen dataor the program at thehost so that a constant ofup to 8 digits suffices.(Refer to 6-9.)489System Installer OperationAppendix BAPPENDIX BSystem Installer OperationThe Support Tool is provided with the “system installer” which installs the systemprogram at a PT.Version up of the PT system program or installation of new communication programs in a PT are possible by installing the system program.Reference: Version up (version up to “–V1” type (system program Ver.2.1)) of NT31, NT31C,NT631, NT631C without “–V1” is possible by installing the system program whichis supplied with the Support Tool (Ver.3.2).For details of the conversion method, refer to Appendix A “Data Conversion”.In this case, however, the following function can not be used.
32 dot high-definition font (Refer to 6–1“Settings for text display”) Font type ISO8859–1(Refer to 3–3 “Font Type” and Appendix J) Memory unit system transmission (Refer to operation manual of NT31, NT31C,NT631, NT631C with “-V1”)To reuse the existing NT31, NT31C, NT631, NT631C screen data, the screen datashould be converted to the data for system program Ver.2.1 beforehand.Applicable PT ModelsThe system installer is used to install the system program in the following PT models.NT11S, NT30, NT30C, NT31, NT31C, NT620S, NT620C/NT625C, NT631,NT631CNoteFor the individual PC (PLC) models, always install the system program of the specific PT model.