H134-E1-01A E5_N UsersManual (986777), страница 32
Текст из файла (страница 32)
. . . .1956-7-1Thermocouple or Infrared Temperature Sensor . . . . . . . . . . . . . . . .1956-7-2Platinum Resistance Thermometer . . . . . . . . . . . . . . . . . . . . . . . . . .1966-7-3Analog Input . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .196183Section 6-1Parameter Structure6-1Parameter Structure• To execute user calibration, enter the password “1201” at the “move tocalibration level” parameter in the advanced function setting level. Themode will be changed to the calibration mode, and adj will be displayed.• The “move to calibration level” parameter may not be displayed when theuser is doing the calibration for the first time. If this happens, set the “initial/communications protect” parameter in the protect level to 0 beforemoving to the advanced function setting level.• The calibration mode is ended by turning the power OFF.• The parameter calibrations in the calibration mode are structured asshown below.Controllers with Thermocouple/Resistance Thermometer Multi-inputsAdvanced Function SettingLeveladjMoves automatically according to input type.30Platinum resistancethermometer0: Pt1001: Pt1002: Pt1003: JPt1004: JPt100Thermocouple or infraredtemperature sensor5: K7: J11: E12: L15: N19: K140F/60C20: K240F/120C21: K280F/140C22: K440F/220C23: 0 to 50 mVp390p280t 54t 24c 54p 10p 10t -6t -6t -6pb10pb10c 54pb 0pb 0c -6e20c454345444083e26b4543b9a5298845444083no020029be35b8stre220ba13bias1846: K8: J9, 10: T13, 14: U16: R17: S18: BAnalog inputbias35b8b9as2988Section 6-1Parameter StructureControllers with Analog InputsAdvanced FunctionSetting Leveladj30Moves automatically according to input type.Current inputVoltage input0: 4 to 20 mA1: 0 to 20 mA2: 1 to 5 V3: 0 to 5 V4: 0 to 10 Va 201v 52v10a1v 12v 1c8e7c7c314677sac0b1044ad9strnoWhen calibration has been performed after purchase, the user calibrationinformation shown in the following illustration will be displayed when moving tothe calibration level..adj30A dot is displayed.185Section 6-2User Calibration6-2User CalibrationThe E5CN/CN-U/AN/EN is correctly calibrated before it is shipped from thefactory, and normally need not be calibrated by the user.If, however, it must be calibrated by the user, use the parameters for calibrating temperature input and analog input.
OMRON, however, cannot ensure theresults of calibration by the user. Also, calibration data is overwritten with thelatest calibration results. The default calibration settings cannot be restoredafter user calibration. Perform user calibration with care.6-2-1Calibrating InputsThe input type selected in the parameter is used for calibration. The inputtypes are as follows:Controllers with Thermocouple/Resistance Thermometer Multi-inputs• Thermocouple:14 types• Infrared temperature sensor:4 types• Analog input:1 type• Platinum resistance thermometer: 5 typesControllers with Analog Inputs• Current input: 2 types• Voltage input: 3 types6-2-2Registering Calibration DataThe new calibration data for each item is temporarily registered.
It can be officially registered as calibration data only when all items have been calibratedto new values. Therefore, be sure to temporarily register all items when youperform the calibration. When the data is registered, it is also recorded thatuser calibration has been performed.Prepare separate measuring devices and equipment for calibration. Fordetails on how to handle measuring devices and equipment, refer to therespective instruction manuals.6-3Thermocouple Calibration (Thermocouple/ResistanceThermometer Input)• Calibrate according to the type of thermocouple: thermocouple 1 group(input types 5, 7, 11, 12, 15) and thermocouple 2 group (input types 6, 8,9, 10, 13, 14, 16, 17, 18, 19, 20, 21, 22).• When calibrating, do not cover the bottom of the Controller.
Also, do nottouch input terminals/pins (terminals 4 and 5 on the E5CN, pins 1 and 2on the E5CN-U, and pins 17 and 18 on the E5AN/EN) or compensatingconductors.186Section 6-3Thermocouple Calibration (Thermocouple/Resistance Thermometer Input)6-3-1PreparationsE5CN9Input power supply10STV−4Cold junctioncompensator+50°C/32°FCompensating conductorE5CN-U10Input power supply11STV−2Cold junctioncompensator+10°C/32°FCompensating conductor1E5AN/ENSTVInput power supply2− 17Cold junctioncompensator+ 180°C/32°FCompensating conductor• Set the cold junction compensator designed for compensation of internalthermocouples to 0°C.
Make sure that internal thermocouples are disabled (i.e., that tips are open).• In the above figure, STV indicates a standard DC current/voltage source.• Use the compensating conductor designed for the selected thermocouple. When thermocouples R, S, E, or B or an infrared temperature sensoris used, the cold junction compensator and the compensating conductorcan be substituted with the cold junction compensator and the compensating conductor for thermocouple K.■ Connecting the Cold Junction CompensatorCorrect process values cannot be obtained if you touch the contact ends ofthe compensating conductor during calibration of a thermocouple.
Accordingly, short-circuit (enable) or open (disable) the tip of the thermocouple insidethe cold junction compensator as shown in the figure below to create a contact or non-contact state for the cold junction compensator.Cold junction compensatorShort-circuitE5CNE5CN-UE5ANE5EN0°C/32°FCompensating conductorE5CNE5CN-UE5ANE5ENCold junction compensator0°C/32°FOpenCompensating conductor187Section 6-3Thermocouple Calibration (Thermocouple/Resistance Thermometer Input)In this example, calibration is shown for a Controller with a Thermocouple/Resistance Thermometer Multi-input, with thermocouple/infrared temperaturesensor set as the input type.1,2,3... 1.
Connect the power supply.2. Connect a standard DC current/voltage source (STV), precision digitalmultimeter (DMM), and contact junction compensator (e.g., a zero controller as in the figure) to the thermocouple input terminals, as shown inthe figure below.STV−DMM+Leave open.ZerocontrollerOUTPUTadj30Input types 5, 7, 11, 12, 15:t-54b9a5Input types 6, 8, 9, 10, 13, 14, 16,17, 18, 19, 20, 21, 22:t-24e220INPUTCompensating conductor of currentlyselected thermocoupleUse K thermocouple compensatingconductor for E, R, S, and B thermocouplesand for an infrared temperature sensor.3. Turn the power ON.4. Move to the calibration level.This starts the 30-minute aging timer. This timer provides an approximatetimer for aging.
After 30 minutes have elapsed, the No. 2 display changesto 0. You can advance to the next step in this procedure even if 0 is notdisplayed.5. When the M key is pressed, the status changes as shown to the left.The No. 2 display at this time shows the currently entered count value inhexadecimal. Set the STV as follows:• Input types 5, 7, 11, 12, 15 : Set to 54 mV.• Input types 6, 8, 9, 10, 13, 14, 16, 17, 18, 19, 20, 21, 22: Set to 24 mV.Allow the count value on the No. 2 display to fully stabilize, then press theD key to temporarily register the calibration settings.If this count value is outside of the specified range, the No. 2 display willflash and the count value will not be temporarily registered.6.
When the M key is pressed, the status changes as shown to the left.Set the STV to −6 mV.Allowthe count value on the No. 2 display to fully stabilize, then press the2988D key to temporarily register the calibration settings.If this count value is outside of the specified range, the No. 2 display willflash and the count value will not be temporarily registered.Input types 6, 8, 9, 10, 13, 14,7. Press the M key. The display changes as shown on the left for input types16,17, 18, 19, 20, 21, and 22 only:6, 8, 9, 10, 13, 14, 16, 17, 18, 19, 20, 21, and 22. Set the STV to 54 mV.Allow the count value on the No.
2 display to fully stabilize, then press theD key to temporarily register the calibration settings.Ifthis count value is outside of the specified range, the No. 2 display willba13flash and the count value will not be temporarily registered.t--6c-54188Section 6-3Thermocouple Calibration (Thermocouple/Resistance Thermometer Input)Press the M key. The display changes as shown on the left for input types6, 8, 9, 10, 13, 14, 16, 17, 18, 19, 20, 21, and 22. Set the STV to −6 mV.Allow the count value on the No.
2 display to fully stabilize, then press theD key to temporarily register the calibration settings.If this count value is outside of the specified range, the No. 2 display willflash and the count value will not be temporarily registered.9. When the M key is pressed, the status changes as shown to the left.Input types 6, 8, 9, 10, 13, 14,8.16,17, 18, 19, 20, 21, and 22 only:c--629bebias35b810. Change the wiring as follows:Open in non-connected stateSTV−DMM+Short-circuitZerocontrollerOUTPUTINPUTCompensating conductor of currentlyselected thermocoupleUse K thermocouple compensatingconductor for E, R, S, and B thermocouplesand for an infrared temperature sensor.Disconnect the STV to enable the thermocouple of the cold junction compensator.
When doing this, be sure to disconnect the wiring on the STVside.strno11. Allow the count value on the No. 2 display to fully stabilize, then press theD key to temporarily register the calibration settings.12. When the M key is pressed, the status changes as shown to the left.The data to be temporarily registered is not displayed if it is not complete.Press the U key. The No. 2 display changes to yes. Release the key andwait two seconds or press the M key.
This stores the temporarily registered calibration data to EEPROM. To cancel the saving of temporarilyregistered calibration data to EEPROM, press the M key (while no is displayed in the No. 2 display) without pressing the U key.13. The calibration mode is ended by turning the power OFF.189Platinum Resistance Thermometer Calibration (Thermocouple/Resistance Thermometer Input)6-4Section 6-4Platinum Resistance Thermometer Calibration(Thermocouple/Resistance Thermometer Input)In this example, calibration is shown for Controller with a Thermocouple/Resistance Thermometer Multi-input, with a resistance thermometer set asthe input type.Use connecting wires of the same thickness.1,2,3... 1.















