The following diagram shows the effect on data after passing through the digital filter:FunctionPV before passing through filterAPV after passing through filter0.63 A(Timeconstant)TimeInput digital filterSetting range0.0 to 999.9UnitSecondDefault0.0SettingpvadAdditional PV DisplayThis parameter adds a display at the beginning of the operation level for theprocess value (PV). If there is no need to display the set point, use this to display only the present temperature.FunctionSet to ON to display, and OFF to not display.Setting rangeon: Displayed, off: Not displayedDefaultoffSettingo-dpMV DisplayThis parameter is used to display the manipulated variable (MV).FunctionThe manipulated variable is displayed when the “MV monitor (heating) and(cooling)” parameters are set to ON, and not displayed when these parameters are set to OFF.Setting rangeon: Displayed, off: Not displayedDefaultoffSetting■ Related ParametersSee166MV monitor (heating): Page 127, MV monitor (cooling): Page 128 (operationlevel)Section 5-7Advanced Function Setting LevelretAutomatic Display Return Time• In the operation level or adjustment level, the display automatically returnsto the PV/SP if there are no key operations for the time set for this parameter.Function• The automatic display return time is disabled when the parameter is set toOFF.
(In that case, the display will not be automatically switched.)Setting rangeOFF, 1 to 99UnitSecondDefaultoffSettinga1ltAlarm 1 LatchAlarm 1 must be assigned, and thealarm 1 type must not be 0.a2ltAlarm 2 LatchAlarm 2 must be assigned, and thealarm 2 type must not be 0.a3ltAlarm 3 LatchAlarm 3 must be assigned, and thealarm 3 type must not be 0.Function• When a parameter is set to ON, once the alarm function has turned ON itis held until the power is turned OFF.
The latch can be canceled, however,by switching to the initial setting level, communications setting level,advanced function setting level, or calibration level.• If alarm outputs are set to “close in alarm,” the outputs are kept closed. Ifthey are set to “open in alarm,” they are kept open.Setting rangeon: Enabled, off: DisabledDefaultoffSetting■ Related ParametersSeeAlarm value 1 to 3: Page 124 to 125, Alarm value upper limit 1 to 3: Page 126to 127, Alarm value lower limit 1 to 3: Page 126 to 127 (operation level)Alarm 1 to 3 type (initial setting level): Page 152 to 154Standby sequence reset: Page 161, Alarm 1 to 3 open in alarm: Page 162,Alarm 1 to 3 hysteresis: Page 163 (advanced function setting level)167Section 5-7Advanced Function Setting LevelprltMove to Protect Level Time• This parameter sets the key pressing time required to move to the protectlevel from the operation level or the adjustment level.FunctionSetting range1 to 30UnitSecondDefault3Setting■ Related ParametersSeeseroOperation/adjustment protect, initial setting/communications protect, settingchange protect (protect level): Page 116Input Error OutputAlarm 1 must be assigned.• When this parameter is set to ON, alarm 1 output turns ON for inputerrors.The alarm 1 operation indicator will not light.Function• The alarm 1 output is an OR output of alarm 1, HBA burnout/HS alarm,and input error.• Output is turned OFF when switching to the initial setting level, communications setting level, advanced function setting level, or calibration level.Setting rangeon: Enabled, off: DisabledDefaultoffSettingcjcCold Junction Compensation MethodInput type must be thermocouple orinfrared temperature sensor• Specifies whether cold junction compensation is to be performed internally by the Controller or to be performed externally when the input typesetting is to between 5 and 22.Function• The cold junction compensation external setting is enabled when the temperature difference is measured using two thermocouples or two ES1BSensors.Setting rangeon: Internally, off: ExternallySetting■ Related ParameterSee168Input type (initial setting level): Page 146DefaultonSection 5-7Advanced Function Setting LevelrlrvCommunications must be supported.CompoWay/F must be selected asthe protocol.MB Command Logic Switching• .This parameter switches the logic of the MB command (communicationswriting switch) for the SYSWAY communications protocol• The MB command (communications writing switch) is the equivalent ofthe MB command (remote/local switch) of the E5@J.Function• The setting indicated by the shaded area is the default (same logic asE5@J).SetvalueSettingOFFONText data of MB command0000Communications writing enabled(remote mode selection)Communications writing disabled(local mode selection)0001Communications writing disabled(local mode selection)Communications writing enabled(remote mode selection)(Terms in parentheses () are the terms used on the E5@J.)■ Related ParametersSeeCommunications writing (adjustment level): Page 131Protocol setting (communications setting level): Page 182colrPV Change ColorUse the PV color change function to change the color of the PV display (No.
1display).There are three display colors, orange, red, and green, and you can selectfrom the following three modes and eight types.Function• Constant: This mode displays orange, red, or green all the time.• Linked to Alarm 1: This mode switches the PV display color from red togreen when alarm 1 turns ON or from green to red when alarm 1 turnsON.• Linked to PV stable band: This mode switches the PV display colorbetween red outside the PV stable band and green within PV stable band,or between green outside the PV stable band and red within PV stableband. Set the PV stable band in the “PV stable band” parameter in theadvanced function setting level.• The default is red (red).The following table shows the display functions that can be set using the PVcolor change function.SettingModeConstantSettingFunctionPV change colororgOrangeConstant: OrangeredRedConstant: RedgrnGreenConstant: GreenApplication exampleTo match the display colorwith other Controller modelsTo match the display colorwith other Controller modelsTo match the display colorwith other Controller models169Section 5-7Advanced Function Setting LevelModeLinked toalarm 1SettingFunctionPV change colorApplication exampleAlarmvalueONALM1 litPVOFFSPALM1 not litALM1 litApplication exampler-gRed toGreenRedGreenTo display the PV reachedsignalg-rGreen toRedGreenRedTo display error signalsLinked toPV stablebandWithinWithinPV stable PV stablebandbandLowWithinHighPVSPr-g.rg-o.ro-g.rRed toGreen toRedGreen toOrange toRedOrange toGreen toRedLowRedPV stable bandGreenHighRedApplication exampleTo display stable statusGreenOrangeRedTo display stable statusRedTo display stable statusOrange Green■ Related ParametersSeepv-bPV stable band (advanced function setting level): Page 170PV Stable BandThis parameter sets the PV stable band width within which the PV displaycolor is changed.Function• When the mode to link to the PV stable band is selected with the “PVchange color” parameter, the PV display color will change according towhether the present value (PV) is lower than, within, or higher than the PVstable band, as shown in the following figure.• There is a fixed hysteresis of 0.2 (°C or °F).PV stable PV stablebandbandLowWithinHighPV0.2 (°C or °F)170SP0.2 (°C or °F)When analog inputs are used: 0.02 (%FS)Section 5-7Advanced Function Setting LevelSettingNoteModelsControllers with Thermocouple/Resistance Thermometer Multi-inputsSetting range0.1 to 999.9Unit°C or °F(See note.)Default5.0Controllers with Analog Inputs0.01 to 99.99%FS5.00Set “none” as the unit for Controllers with Analog Inputs.■ Related ParameterSeePV change color (advanced function setting level): Page 169a1onAlarm 1 ON DelayAlarm 1 must be assigned, and thealarm 1 type must not be 0 or 12.a2onAlarm 2 ON DelayAlarm 2 must be assigned, and thealarm 2 type must not be 0.a3onAlarm 3 ON DelayAlarm 3 must be assigned, and thealarm 3 type must not be 0.Alarm 1, 2, or 3 outputs are prevented from turning ON until after the delaytimes set in these parameters have elapsed.• Set the time for which the ON delay is to be enabled.• To disable the ON delay, set 0.FunctionSetting range0 to 999UnitSecondDefault0Setting■ Related ParametersSeeAlarm 1 to 3 type (initial setting level): Page 152 to 154171Section 5-7Advanced Function Setting Levela1ofAlarm 1 OFF DelayAlarm 1 must be assigned, and thealarm 1 type must not be 0 or 12.a2ofAlarm 2 OFF Delaya3ofAlarm 3 OFF DelayAlarm 2 must be assigned, and thealarm 2 type must not be 0.Alarm 3 must be assigned, and thealarm 3 type must not be 0.Alarm 1, 2, or 3 outputs are prevented from turning OFF until after the delaytimes set in these parameters have elapsed.• Set the time for which the OFF delay is to be enabled.• To disable the OFF delay, set 0.FunctionSetting range0 to 999UnitSecondDefault0Setting■ Related ParametersSeeistpAlarm 1 to 3 type (initial setting level): Page 152 to 154Input Shift TypeThe input type must be thermocouple or resistance thermometer.This parameter sets the shift method for thermocouple or resistance thermometer inputs.• When the input type is thermocouple or resistance thermometer, seteither a 1-point shift or a 2-point shift.FunctionSetting rangeins1: 1-point shift, ins2: 2-point shiftDefaultins1Setting■ Related ParametersSeeTemperature input shift, Upper-limit temperature input shift value, Lower-limittemperature input shift value (adjustment level): Page 136Input type (initial setting level): Page 146172Section 5-7Advanced Function Setting LevelmvseMV at Stop and Error AdditionThe control must be set to 2-PIDcontrol.This parameter sets whether or not the “MV at stop” and “MV at PV error”parameters are to be displayed.• Set whether or not the “MV at stop” and “MV at PV error” parameters areto be displayed.FunctionSetting rangeon: Displayed, off: Not displayedDefaultoffSetting■ Related ParametersSeeamadMV at stop, MV at PV error (adjustment level): Page 142Auto/Manual Select AdditionThe control must be set to 2-PIDcontrol.This parameter sets whether the “auto/manual switch” parameter is to be displayed.• Set whether the “auto/manual switch” parameter is to be displayed.FunctionSetting rangeon: Displayed, off: Not displayedDefaultoffSetting■ Related ParameterSeeAuto/manual switch (operation level): Page 120173Section 5-7Advanced Function Setting LevelrtThe control must be set to 2-PIDcontrol.The input type must be set to temperature input.RTThis parameter executes robust tuning (RT).• When AT or ST is executed with RT selected, PID constants are automatically set which make it hard for control performance to degenerate evenwhen control object characteristics are changed.Function• Even when hunting occurs for PID constants when AT or ST is executedin normal mode, it is less likely to occur when AT or ST is executed in RTmode.Setting rangeon: RT function OFF, off: RT function ONDefaultoffSetting■ Related ParametersSeeAT execute/cancel: Page 131, Proportional band, Integral time, Derivativetime: Page 138 (adjustment level)PID ON/OFF: Page 149, ST: Page 150 (initial setting level)hsuHeater burnout and HS alarms mustbe supported.Alarm 1 must be assigned.HS Alarm Use• Set this parameter to use HS alarms.FunctionSetting rangeon: Enabled, off: DisabledSetting174DefaultonSection 5-7Advanced Function Setting LevelhslHeater burnout and HS alarms mustbe supported.Alarm 1 must be assigned.The “HS alarm” parameter must beset to ON.HS Alarm Latch• When this parameter is set to ON, the HS alarm is held until either of thefollowing conditions is satisfied.FunctionaThe HS alarm current is set to 50.0 A.bThe power is turned OFF then back ON again (i.e., power is reset).• Output is turned OFF when switching to the initial setting level, communications setting level, advanced function setting level, or calibration level.Setting rangeon: Enabled, off: DisabledDefaultoffSetting■ Related ParameterSeehshHS alarm use (advanced function setting level): Page 174Heater burnout and HS alarms mustbe supported.Alarm 1 must be assigned.The “HS alarm” parameter must beset to ON.The “HS alarm latch” must be set toOFF.HS Alarm Hysteresis• This parameter sets the hysteresis for HS alarms.FunctionSetting range0.1 to 50.0UnitADefault0.1Setting■ Related ParameterSeeHS alarm use (advanced function setting level): Page 174175Section 5-7Advanced Function Setting LevellbaAlarm 1 must be assigned.The alarm type must be set to 12(LBA).LBA Detection TimeThis parameter enables or disables the LBA function and sets the detectiontime interval.• Set the time interval for detecting loop burnouts.• To disable the LBA function, set 0.FunctionSetting range0 to 9999UnitSecondDefault0Setting■ Related ParametersSeeAlarm 1 type (initial setting level): Page 152LBA level: Page 176, LBA band: Page 177 (advanced function setting level)lbalAlarm 1 must be assigned.The alarm type must be set to 12 (LBA).The LBA detection time must not be 0.LBA Level• This parameter sets the LBA level.• If the deviation between the SP and PV exceeds the LBA level, a loopburnout is detected.FunctionModelsControllers with Thermocouple/Resistance Thermometer Multi-inputsControllers with Analog InputsSettingNoteSetting range0.1 to 999.90.01 to 99.99Unit°C or °F(See note.)%FSDefault8.010.00Set “none” as the unit for Controllers with Analog Inputs.■ Related ParametersSeeProcess value/set point (operation level): Page 120Alarm 1 type (initial setting level): Page 152LBA detection time: Page 176, LBA band: Page 177 (advanced function setting level)176Section 5-7Advanced Function Setting LevellbabAlarm 1 must be assigned.The alarm type must be set to 12(LBA).The LBA detection time must not be0.LBA Band• This parameter sets the LBA band.• If a control deviation greater than the LBA band is not reduced when theLBA level is exceeded, an loop burnout is detected.FunctionSettingNoteModelsControllers with Thermocouple/Resistance Thermometer Multi-inputsSetting range0.0 to 999.9Unit°C or °F(See note.)Default3.0Controllers with Analog Inputs0.00 to 99.99%FS0.20Set “none” as the unit for Controllers with Analog Inputs.■ Related ParametersSeeProcess value/set point (operation level): Page 120Alarm 1 type (initial setting level): Page 152LBA detection time, LBA level (advanced function setting level): Page 176out1Control Output 1 AssignmentThe transfer output type must be setto OFF when the control output is acurrent output.• This parameter sets the function to be assigned to control output 1.FunctionSetting rangeNone: No function is assigned to control output 1.o:Heating control output is output.SettingDefaultoc-o: Cooling control output is output.