(See note 1.)alm1: Alarm 1 is output. (See note 2.)alm2: Alarm 2 is output. (See note 2.)alm3: Alarm 3 is output. (See note 2.)p.end: Program end is output. (See notes 2 and 3.)Note(1) If c-o is assigned for standard control, a value equivalent to 0% is output.(2) Can be selected for relay and voltage outputs only.(3) Can be selected only when the program pattern is not set to OFF.■ Related ParametersSeeStandard or heating/cooling: Page 150, Program pattern: Page 151, Transferoutput type: Page 155 (initial setting level)177Section 5-7Advanced Function Setting Levelout2Control Output 2 AssignmentControl output 2 must be assigned.• This parameter sets the function to be assigned to control output 2.FunctionSetting rangeDefaultnone: No function is assigned to control output 2.o:Heating control output is output.Settingc-o: Cooling control output is output.
(See note 1.)alm1: Alarm 1 is output.none(See note3.)alm2: Alarm 2 is output.alm3: Alarm 3 is output.p.end: Program end is output. (See note 2.)Note(1) If c-o is assigned for standard control, a value equivalent to 0% will beoutput.(2) Can be selected only when the program pattern is not set to OFF.(3) If the “standard or heating/cooling” parameter is set to heating/coolingcontrol, control automatically switches to c-o.■ Related ParametersSeealm1Standard or heating/cooling: Page 150, Program pattern: Page 151, (initialsetting level)Alarm 1 AssignmentAlarm output 1 must be assigned.• This parameter sets the function to be assigned to alarm output 1.FunctionSetting rangenone: No function is assigned to alarm output 1.o:c-o:SettingHeating control output is output.Cooling control output is output.
(See note 1.)Defaultalm1(See note3.)alm1: Alarm 1 is output.alm2: Alarm 2 is output.alm3: Alarm 3 is output.p.end: Program end is output. (See note 2.)Note(1) If c-o is assigned for standard control, a value equivalent to 0% will beoutput.(2) Can be selected only when the program pattern is not set to OFF.(3) If a setting is changed when the “program pattern” parameter is not set toOFF, control automatically switches to p.end.See178■ Related ParameterProgram pattern (initial setting level): Page 151Section 5-7Advanced Function Setting Levelalm2Alarm 2 AssignmentAlarm output 2 must be assigned.• This parameter sets the function to be assigned to alarm output 2.FunctionSetting rangenone: No function is assigned to alarm output 2.o:Heating control output is output.Settingc-o: Cooling control output is output.
(See note 1.)alm1: Alarm 1 is output.Defaultalm2(See note3.)alm2: Alarm 2 is output.alm3: Alarm 3 is output.p.end: Program end is output. (See note 2.)Note(1) If c-o is assigned for standard control, a value equivalent to 0% will beoutput.(2) Can be selected only when the program pattern is not set to OFF.(3) If the “standard or heating/cooling” parameter is set to heating/coolingcontrol when there is no control output 2 (E5CN/CN-U), control automatically switches to c-o.■ Related ParametersSeeStandard or heating/cooling: Page 150, Program pattern: Page 151, (initialsetting level)179Section 5-7Advanced Function Setting Levelalm3Alarm output 3 must be assigned(E5AN and E5EN only).Alarm 3 Assignment• This parameter sets the function to be assigned to alarm output 3.FunctionSetting rangeDefaultnone: No function is assigned to alarm output 3.o:c-o:Settingalm3(See note3.)Heating control output is output.Cooling control output is output. (See note 1.)alm1: Alarm 1 is output.alm2: Alarm 2 is output.alm3: Alarm 3 is output.p.end: Program end is output.
(See note 2.)Note(1) If c-o is assigned for standard control, a value equivalent to 0% will beoutput.(2) Can be selected only when the program pattern is not set to OFF.(3) If the “standard or heating/cooling” parameter is set to heating/coolingcontrol when there is no control output 2 (E5AN/EN), control automatically switches to c-o.■ Related ParametersSeecselFunctionStandard or heating/cooling: Page 150, Program pattern: Page 151, (initialsetting level)Character Select• This parameter switches the characters to be displayed.The following two types of characters can be displayed.11-segment display7-segment displaySetting rangeon: 11-segment display, off: 7-segment displaySetting180DefaultonWhen set to on, an 11-segment display is used.Section 5-7Advanced Function Setting Levelt-uThe “program pattern” parametermust not be set to OFF.Soak Time Unit• Set the soak time unit for the simple program function.FunctionSetting rangeDefaultm: Minutes, h: HoursmSetting■ Related ParametersSeeProgram start, Soak time remain (operation level): Page 123Soak time, Wait band (adjustment level): Page 141Program pattern (initial setting level): Page 151alspAlarm SP SelectionAlarm 1, 2, and 3 functions must beassigned.The “SP ramp set value” and “ST”parameters must not be set to OFF.The alarm type must set to a deviation alarm.This parameter sets whether the set point that triggers a deviation alarm during SP ramp operation is to be the ramp SP or target SP.• Set whether the set point that triggers a deviation alarm is the ramp SP ortarget SP.FunctionSetting rangesp-m: Ramp SP, sp: SPDefaultsp-mSetting■ Related ParametersSeecmovSP ramp set value (adjustment level): Page 143ST (initial setting level): Page 150Move to Calibration LevelInitial setting/communications protectmust be 0.This parameter sets the password to move to the calibration level.• Set the password to move to the calibration level.
The password is 1201.FunctionSee• Move to the calibration level either by pressing the M key or O key or bywaiting for two seconds to elapse.■ Related ParameterInitial setting/communications protect (protect level): Page 116181Section 5-8Communications Setting Level5-8pselu-nobpslensbitprtysdwtCommunications Setting LevelProtocol SettingCommunications Unit No.Communications Baud RateCommunications Data LengthCommunications Stop BitsCommunications ParitySend Data Wait TimeCommunications must be supported.CompoWay/F must be selected as the protocol.CompoWay/F must be selected as the protocol.• Each parameter is enabled when the power is reset.Function• Match the communications specifications of the E5@N and the host computer.
If multiple devices are connected, ensure that the communicationsspecifications for all devices in the system (except the Communicationsunit number) are the same.ItemSettingSymbolSet valuesSettingspselcwf, modCompoWay/F(SYSWAY), ModbuscwfCommunicationsUnit No.Communicationsbaud rateCommunicationsdata lengthStop bitsu-no0 to 990 to 991bps1.2, 2.4, 4.8, 9.6,19.2, or 38.4 (kbit/s)7, 8 (bit)1.2, 2.4, 4.8, 9.6,19.2, or 38.4 (kbit/s)7, 8 (bit)9.6sbit1, 21, 22CommunicationsparitySend data wait timeprtynone, even, oddNone, Even, Oddevensdwt0 to 990 to 99 (ms)20len■ Related ParameterSee182DefaultProtocol settingCommunications writing (adjustment level): Page 1317SECTION 6CALIBRATIONThis section describes how the user can calibrate the E5CN and E5CN-U Digital Temperature Controllers.6-16-26-36-4Parameter Structure.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .184User Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1866-2-1Calibrating Inputs . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .1866-2-2Registering Calibration Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .186Thermocouple Calibration (Thermocouple/Resistance Thermometer Input) .1866-3-1Preparations . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .187Platinum Resistance Thermometer Calibration(Thermocouple/Resistance Thermometer Input) . . . . . . . . . . . . . . . . . . . . . .1906-5Analog Input Calibration (Thermocouple/Resistance Thermometer Input) . .1926-6Calibrating Analog Input (Analog Input) . . . . . . . . . . . . . . . . . . . .
. . . . . . . .1936-6-1Calibrating a Current Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1936-6-2Calibrating a Voltage Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1946-7Checking Indication Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .