H136-E1-01A E5_N Datasheet (986779), страница 4
Текст из файла (страница 4)
(Maintain thespecified mounting space betweenControllers.)• To mount the Controller so that it iswaterproof, insert the waterproofpacking onto the Controller.• When two or more Controllers aremounted, make sure that thesurrounding temperature does notexceed the allowable operatingtemperature specified in thespecifications.Panel CutoutGroup MountedMounted Separately(48 × number of units −2.5) +1.00648 × 4870.514.245 +0.6044.8 × 44.85860 min.45 +0.60Mounting Adapter(Accessory)14Digital Temperature Controllers E5CN/E5CN-U45 +0.60• Recommended panel thickness is 1 to5 mm.• Group mounting is not possible in thevertical direction.
(Maintain thespecified mounting space betweenControllers.)• When two or more Controllers aremounted, make sure that thesurrounding temperature does notexceed the allowable operatingtemperature specified in thespecifications.■ AccessoriesUSB-Serial Conversion Cable (Sold Separately)E58-CIFQ1(2,100)LED indicator (SD)250USB connector (type A plug)1,765Serial connectorLED indicator (RD)Terminal Cover48E53-COV1048.822Note: The suffix “-500” is added to the model number of eachController provided with a E53-COV10 Terminal Cover.9.1Current Transformers (Sold Separately)E54-CT121152.85.8 dia.7.525310.540Two, 3.5 dia.1030E54-CT3 AccessoryE54-CT32.36 dia.Connection Example• Armature30ArmaturePlug12 dia.9Approx.
3 dia.Lead40 × 4018• PlugTwo, M3 (depth: 4)Approx. 6 dia.1530(22)Digital Temperature ControllersE5CN/E5CN-U15Adapter (Sold Separately)Note: Use this Adapter when the panel has already been prepared for the E5B@.Y92F-45Fixture (Accessory)764.769.6 to 77.672 × 7267 × 67 87Mounted to E5CNPanel (1 to 8 mm)72 × 7248 × 482.24.777.3 (to back of E5CN)E5CN-U Wiring Socket (Sold Separately)Front-connecting SocketEleven, M3.5 × 7.5sems screwsP2CF-113Terminal Layout/Internal Connections(Top View)4.57.88 7 6 5Mounting Holes4Two, 4.5 dia. mounting holes35.470 max.Two,4.5-dia.holes49310 11 1 240±0.2Note: Can also be mounted to a DIN track.50 max.31.2 max.Note: A model with finger protection (P2CF-11-E) is also available.Back-connecting SocketP3GA-1127 dia.473Terminal Layout/Internal Connections(Bottom View)5 6 7 844525.6392 1 11 10454.5 16.3 6.268.7Note: 1.
Using any other sockets will adversely affect accuracy. Use only the specified sockets.2. A Protective Cover for finger protection (Y92A-48G) is also available.16Digital Temperature Controllers E5CN/E5CN-UDigital Temperature ControllersE5ENThis Best-selling General-purposeTemperature Controller Is Now Even Better.USB-Serial Conversion Cable and SupportSoftware Are Also Available.• Controllers now available with analog inputs.• Faster sampling at 250 ms.• Transfer output provided for easy output to recorders.• Voltage outputs (to drive SSRs) for both heating and coolingcontrol.• Models available with three-phase heater burnout detection andSSR fault detection.• Manual output provided.• Controller available with long-life relay output.• Models available with external power supply for ES1B InfraredThermosensor.• Easy setting with 11-segment displays.• Connect to either a thermocouple or platinum resistancethermometer with the same model.• Easily see the status from a distance with PV display with threecolor switching function.Note: Refer to page 42 for information on changes in comparison toprevious models.Note: Refer to Precautions on page 45.FeaturesImproved Functions for a Wider Range of ApplicationControl Analog Values, such as Pressures, Flowrates,and LevelsVoltage Outputs (to Drive SSRs) for Both Heating andCooling Control.The E5EN Series now also includes models that accept analoginputs, enabling control applications other than for temperature,including pressure, flowrate, level, humidity, and weight control.Voltage outputs can be used for both heating and cooling for Modelswith Two Control Outputs.Faster Sampling at 250 msThe previous sampling time of 500 ms has been reduced by half to250 ms.
This enables the E5EN to handle application requiring evengreater response speed and accuracy.Easy Connector to a RecorderThree-phase Heater Burnout DetectionWith Models with Three-phase Heater Burnout and SSR FailureDetection, two current transformers can be connected to detect bothheater burnout and SSR failure at the same time, reducing costsbecause a separate heater burnout alarm device is not required.SSR failure detection can be used even with Models with Singlephase Heater Burnout Alarms.A transfer output now makes it easy to connect to a recorder or PLCAnalog I/O Unit.E58-CIFQ1 USB-Serial Conversion Cable for Computer ConnectionA personal computer connection is possible for models without communications.The CX-Thermo Support Software (sold separately) can be used to set parameters, monitor operation, andparameter masks.
(CX-Thermo support of the E5EN is scheduled for March 2005.)Specifications: page 20, Dimensions: page 26Digital Temperature ControllersE5EN17Model Number Structure■ Model Number LegendE5EN-@@@M@-5001 2 3 4 53. Heater burnout/SSR failureOutput 2/External power supply for ES1BH:Heater burnout/SSR failure detection (1 CT)HH: Heater burnout/SSR failure detection (2 CT)Q:Voltage for driving SSRY:Long-life RelayP:External Power supply for ES1BBlank: Not available4. Option Unit5. Input typeT: Thermocouple/platinum resistance thermometer (multi-input)L: Analog input1. Output 1 typeR: RelayQ: Voltage for driving SSRC: Current2. Number of alarms3: 3 alarmsOrdering Information■ Temperature Input (Multi Input) Standard ModelsSizePower supplyvoltage100 to 240 VAC1/8 DIN48 × 96 × 78 (W × H × D)Number ofalarm points3Control outputRelayVoltage (for driving SSR)24 VAC/VDC3Heater alarmModelNoE5EN-R3MT-500Yes (1 CT)E5EN-R3HMT-500Yes (2 CT)E5EN-R3HHMT-500NoE5EN-Q3MT-500Yes (1 CT)E5EN-Q3HMT-500Yes (2 CT)E5EN-Q3HHMT-500CurrentNoE5EN-C3MT-500RelayNoE5EN-R3MT-500Voltage (for driving SSR)CurrentYes (1 CT)E5EN-R3HMT-500NoE5EN-Q3MT-500Yes (1 CT)E5EN-Q3HMT-500NoE5EN-C3MT-500■ Temperature Input (Multi Input) 2 Outputs ModelsSizePower supplyvoltage1/8 DIN100 to 240 VAC48 × 96 × 78 (W × H × D)Number ofalarm points3Control output 1RelayControl output 2 Power supply forES1BVoltage (for driving NoSSR)Voltage (for driving Voltage (for drivingSSR)SSR)E5EN-R3QMT-500E5EN-Q3QMT-500Ling-life RelayE5EN-Q3YMT-500CurrentVoltage (for drivingSSR)E5EN-C3QMT-500RelayNoLing-life RelayVoltage (for drivingSSR)18ModelDigital Temperature Controllers E5ENE5EN-C3YMT-500YesE5EN-R3PMT-500E5EN-Q3PMT-500■ Analog Input ModelsSizePower supplyvoltage100 to 240 VAC1/8 DIN48 × 96 × 78 (W × H × D)Number ofalarm points3Control output1Heater alarmRelayNoVoltage (fordriving SSR)NoControl output2NoModelE5EN-R3ML-500E5EN-Q3ML-500CurrentNoE5EN-C3ML-500RelayYes (1 CT)E5EN-R3HML-500Voltage (fordriving SSR)Yes (1 CT)E5EN-Q3HML-500Voltage (fordriving SSR)NoLong-life RelayE5EN-Q3YML-500■ Option UnitsNameFunctionModelCommunication UnitRS-232C CommunicationE53-EN01RS-485 CommunicationE53-EN03Event Input UnitEvent InputE53-AKBDigital Temperature ControllersE5EN19Specifications■ RatingsItemPower supplyvoltage100 to 240 VAC, 50/60 Hz24 VAC, 50/60 Hz or 24 VDCOperating voltage range85% to 110% of rated supply voltagePower consumptionApprox.
10 VASensor inputModels with temperature inputsThermocouple: K, J, T, E, L, U, N, R, S, or BPlatinum resistance thermometer: Pt100 or JPt100Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°CVoltage input: 0 to 50 mVApprox. 5.5 VA (24 VAC)/approx. 4 W (24 VDC)Models with analog inputsCurrent input: 4 to 20 mA or 0 to 20 mAVoltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 VInput impedanceCurrent input: 150 Ω, Voltage input: 1 MΩ (Use a 1:1 connection when connecting the ES2-HB.)ControloutputRelay outputSPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V,10 mAVoltage outputOutput voltage: 12 VDC +15%/−20% (PNP), max.
load current: 40 mA, with short-circuit protection circuit (max.load current of control output 2: 21 mA)Current output 4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 2,700Long-life relayoutputAlarm outputEvent inputSPST-NO, 250 VAC, 3 A (resistive load), electrical life: 1,000,000 operations, load power supply voltage: 75 to250 VAC (DC loads cannot be connected.), minimum applicable load: 5 V, 10 mA, leakage current: 5 mA max.(250 VAC, 60 Hz)SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 1 V, 1 mAContact inputON: 1 kΩ max., OFF: 100 kΩ min.Non-contactinputON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.Outflow current: Approx.
7 mA per pointExternal power supply forES1B12 VDC ±10%, 20 mA, Short-circuit protection provided.Control methodON/OFF control or 2-PID control (with auto-tuning)Setting methodDigital setting using front panel keysIndication method11-segment digital display and individual indicators (7-segments displays also possible)Character height: PV: 14 mm, SV: 9.5 mmOther functionsManual output, heating/cooling control, transfer output (on some models), loop break alarm, multi SP, MVlimiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, etc.Ambient operatingtemperature−10 to 55°C (with no icing or condensation), for 3-year warranty: −10 to 50°CAmbient operating humidity25% to 85%Storage temperature−25 to 65°C (with no icing or condensation)20Digital Temperature Controllers E5EN■ Input RangesThermocouples/Platinum Resistance Thermometers (Multi-inputs)InputTypePlatinum resistancethermometerNamePt100ThermocoupleJPt100KJTELInfrared temperaturesensorUNRSB10 to70°C60 to120°C115 to165°C140 to260°CTemperature range (°C)Settingnumber17001300170013008508500 to 50 mVUsable inthe followingranges byscaling:−1999 to9999 or−199.9 to999.918001800170016001500140013001200110010009008007006005004003002001000−100.0−200.0Analoginput850600500.0500.0500.0400.0400400.0400400.0260100.0100.0120165000019202122901000.0−200−199.9010.0−199.9230−20.0−100−20.0678−20045The applicable standards for the input typesare as follows:001617−100−200−199.99101112−200−199.9−200131415U: Cu-CuNi, DIN 43710-19851823Shaded settings are the default settings.Pt100: IEC 751K, J, T, E, N, R, S, B: IEC 584-1L: Fe-CuNi, DIN 43710-1985Models with Analog InputsInput TypeCurrentVoltageInput specification4 to 20mA 0 to 20 mA 1 to 5 VSetting rangeUsable in the following ranges by scaling:−1999 to 9999, −199.9 to 999.9, −19.99 to 99.99 or −1.999 to 9.999Setting number0120 to 5 V30 to 10 V4Shaded settings are the default settings.Digital Temperature ControllersE5EN21■ Alarm TypesSelect alarm types out of the 12 alarm types listed in the following table.Set valueAlarm typeAlarm output operationWhen X ispositive0Alarm functionOFF1Upper- and lower(See note 1.) limit23Upper limitLower limit4Upper- and lower(See note 1.) limit range5Upper- and lower(See note 1.) limit with standbysequenceOutput OFFXSPXONOFF(See note 2.)LONOFFONOFFSPONOFFHHXCase 3 (Always ON)Absolute-valueupper-limitONOFF9Absolute-valuelower-limitONOFF10Absolute-valueupper-limit withstandby sequenceONOFFAbsolute-valuelower-limit withstandby sequenceONOFFH SPHSP L HH>0, L<0|H| > |L|SPLH<0, L>0|H| ≥ |L|L SPHSP HSPLCase 1(See note 3.)(See note 4.)Case 3 (Always ON)Case 2H<0, L<0LH SPH<0, L>0|H| < |L|SP LHHH>0, L<0|H| > |L|HSPLL SPSPXONOFFSP H LSPXSPX0X0X0X0ONOFFONOFFONOFFONOFFONOFFONOFFXSPXSPX0X0X0X---Digital Temperature Controllers E5ENH>0, L<0|H| ≤ |L|3.