H134-E1-01A E5_N UsersManual (986777), страница 21
Текст из файла (страница 21)
Press the O key for at least one second to move from the initial settinglevel to the operation level.9. Select the “auto/manual switch” parameter by pressing the M key.Operation LevelAuto/manuala-m switchManual Control LevelC250.0100PV/MV10. Press the O key for at least three seconds to move from the operationlevel to the manual control level.Section 4-14Using the Transfer OutputC11.
Press the U or D key to set the manual MV. (In this example, the MV isset to 500%.)2550.0NoteThe manual MV setting must be fixed (see page 12), but valueschanged with key operations are reflected in the control outputimmediately.12. Press the O key for at least one second to move from the manual controllevel to the operation level.Operation LevelC25PV/SP1004-14 Using the Transfer Output4-14-1 Transfer Output Function• If a control output is a linear current output it can be used as a transferoutput. To use the transfer output, set the “transfer output type” parameterto any setting other than OFF.(When the “transfer output type” parameter is set to any setting other thanOFF, the “transfer output upper limit” and “transfer output lower limit”parameters will be enabled.)Transfer Output TypeTransfer output typeOFF (See note 1.)SymboloffSet pointspSet point during SP ramp sp-mNoteSetting range--SP lower limit to SP upper limitSP lower limit to SP upper limitPVpvSensor setting range lower limit to Sensorsetting range upper limit orScaling lower limit to Scaling upper limitMV monitor (heating)mv−5.0 to 105.0 (heating/cooling control: 0.0 to105.0) (See note 2.)MV monitor (cooling)c-mv0.0 to 105.0 (See note 2.)(1) The default is OFF.
If the transfer type is set to OFF, the item assigned inthe “control output 1 assignment” parameter will be output on control output 1.(2) The difference between the transfer output value and the linear currentoutput value is illustrated in the following figure.If the linear output is used as the transfer output when the linear currentoutput type is set to 4 to 20 mA, 4.0 mA will be output for 0% and 20.0 mAwill be output for 100%.When a linear output is used for the control output, 3.7 mA is output for0% and 20.3 mA is output for 100% when the control output for heatingis selected to ensure that the control object is controlled at 0% and 100%.101Section 4-14Using the Transfer OutputOutput current (mA)20.320Transfer output valueControl output43.70MV (%)100(The above graph is for when the linear current output type is set to 4 to 20 mA.)Transfer Scaling• Reverse scaling is possible by setting the “transfer output lower limit”parameter larger than the “transfer output upper limit” parameter.
If the“transfer output lower limit” and “transfer output upper limit” parametersare set to the same value when 4 to 20 mA is set, the transfer output willbe output continuously at 0% (4 mA).• If the SP, SP during SP ramp, or PV is selected, the “transfer output lowerlimit” and “transfer output upper limit” parameters will be forcibly initializedto the respective upper and lower setting limits for changes in the upperand lower limits of the SP limiter and the temperature unit.If the MV for heating or MV for cooling is selected, the “transfer outputlower limit” and “transfer output upper limit” parameters will be initializedto 100.0 and 0.0, respectively, when a switch is made between standardcontrol and heating/cooling control using the “standard or heating/cooling”parameter.• The output current when the linear current type is set to 4 to 20 mA, thetransfer output upper limit is set to 90.0, and the transfer output lower limitis set to 10.0 is shown in the following graph.• For scaling from 0.0% to 100.0%, the output for −5.0 to 0.0 will be thesame value as for 0.0%, and the output for 100.0 to 105.0 will be thesame value as for 100.0%Output current (mA)204MV (%)010Transfer outputlower limit90100Transfer outputupper limit(The above graph is for when the linear current output type is set to 4 to 20 mA.)102Section 4-14Using the Transfer OutputOperating ProcedureThe following procedure sets the transfer output for an SP range of −50 to200.Operation LevelC25PV/SP100Initial Setting Levelin-tInput type1.
Press the O key for at least three seconds to move from the operationlevel to the initial setting level.5Initial Setting Level2. Select the “transfer output type” parameter by pressing the M key.Transfer outputtr-t typeoff3. Press the U key to select sp (set point).tr-tspInitial Setting LevelC4. Select the “transfer output upper limit” parameter by pressing the M key.Transfer outputtr-h upper limit1300C5.
Use the D key to set the parameter to 200. The default is 1300.tr-h200Initial Setting LevelC6. Select the “transfer output lower limit” parameter by pressing the M key.Transfer outputtr-l lower limit-200C7. Use the U key to set the parameter to −50. The default is −200.tr-l-508. To return to the operation level, press the O key for at least one second.Operation LevelC25PV/SP100103Section 4-15Using the Simple Program Function4-15 Using the Simple Program Function4-15-1 Simple Program Function• The simple program function can be used for the following type of control.SPWait bandWait bandSet pointPVSoak timeRSET → STRTEND displayEND outputSelect eitherSTOP or RUN.• The program will start when the “program start” parameter is changedfrom RSET to STRT.
END will be displayed on the No. 2 display and theoutput assigned as the program end output will turn ON after the time setin the “soak time” parameter has expired in the wait band. The “programpattern” parameter can be used to select moving to STOP mode or continuing operation in RUN mode after the program ends.Parameters Related to the Simple Program FunctionParameter nameProgram patternSymbolptrnSet (monitor) valuesOFF, STOP, CONT---Display levelInitial setting levelProgram startSoak timeprstsoakRSET, STRT1 to 9999--min or hOperation levelAdjustment levelSoak time unitt-um (minutes)/h (hours)---Advanced function setting levelWait bandwt-bOFF or 0.1 to 999.9 (See note 2.)Adjustment levelSoak time remainmonitorsktr0 to 9999°C or °F (See notes 1and 2.)min or hNoteUnitOperation level(1) Set for Controllers with Thermocouple/Resistance Thermometer Multi-inputs.
Set “none” as the unit for Controllers with Analog Inputs.(2) The setting unit of the “wait band” parameter is %FS for Controllers withAnalog Inputs and the setting range is OFF or 0.01 to 99.99.104Section 4-15Using the Simple Program FunctionProgram PatternEither of two program patterns can be selected. The simple program operation will not be performed if the “program pattern” parameter is set to OFF.■ Pattern 1 (STOP)Control will stop and the STOP mode will be entered when the program hasended.Wait bandWait bandSet pointPVRSET → STRTSoak timeEND displayEND outputAutomatically switchesfrom RUN to STOP mode.■ Pattern 2 (CONT)Control will continue in RUN mode when the program has ended.Wait bandWait bandSet pointPVRSET → STRTSoak timeRUN mode continues.END displayEND outputThe pattern display and setting range will change as shown in the followingtable when a program mode is set in the “program pattern” parameter.ItemDisplayed parametersControl output 1/2assignmentAlarm 1/2/3 assignmentSetting rangeEvent input assignment 1/2 settingrangeProgram mode not selectedProgram mode selectedThere are no parameters that • Program startare not displayed if a program • Soak timemode is set.• Soak time unit• Wait band• Soak time remainNot assigned.Not assigned.Control output (heating)Control output (heating)Control output (cooling)Control output (cooling)Alarm 1Alarm 1Alarm 2Alarm 2Alarm 3Alarm 3Program end outputNot assigned.RUN/STOPAUTO/MANUALNot assigned.RUN/STOPAUTO/MANUALProgram start (RESET/START)105Section 4-15Using the Simple Program FunctionStarting MethodAny of the following three methods can be used to start the simple program.• Setting the “program start” parameter to STRT.• Turning ON an event input.
(The program start must be assigned to anevent input. See note.)• Starting with an Operation Command using communications. (When theprogram start is not assigned to an event input.)NoteWhen an event input is used to start and reset the simple program, writing isperformed to EEPROM. Be sure to consider the write life (1 million writes) ofthe EEPROM in the system design.
When the program start is assigned to anevent input, the “program start” parameter will function as a monitor display,and the RSET/STRT displays can be used to check when the event input hasstarted or reset the simple program. When this is done, the “program start”parameter functions as a monitor display only and cannot be changed usingkey operations. If the “program pattern” parameter is set to OFF, the eventinput assignment setting will be initialized to “none.”Soak Time and Wait BandWait bandSet pointWait bandPVRSET → STRT(1)(2) (3)(4)(5)Set pointSet pointSoak timeremainThe wait band is the fixed band within which the process value is stable inrespect to the set point. The soak time is measured within the wait band.
Thetimer that measures the soak time operates only when the process value iswithin the wait band around the set point (i.e., SP ± wait band). In the followingdiagram, the timer will be stopped between the start and (1), (2) and (3), and(4) and (5) and will measure the time only between (1) and (2), (3) and (4),and (5) and the end.Note106If the wait band is set to OFF, the wait band will be treated as infinity and thetimer will measure time continuously after changing from RSET to STRT.Section 4-15Using the Simple Program Function4-15-2 Operation at the Program EndDisplay at the Program EndWhen the program ends, the process value will be displayed on the No.















