ZEN-SOFT01-V3 ZEN Support Software_Operation Manual (986766), страница 6
Текст из файла (страница 6)
Enter the save destination and file name and click the Save Button.1.When saving existing ladder programs that have been editedsince they were saved, you can also click the Save Button on theToolbar or select File/Save from the Menu Bar to overwrite the existing file.Section 2-7Printing Ladder Programs2.2-6-2Opening Saved Files1,2,3...2-7The system settings and password set under ZEN/SetProtection will also be saved with the file.1.Click the Open Button on the Toolbar or select File/Open fromthe Menu Bar to open saved files.2.The Open File Dialog Box will be displayed.
Specify the file location and file name and click the Open Button.Printing Ladder Programs2-7-1Print SettingsThis section describes the layout and heading settings that must bemade before printing ladder programs.1,2,3...1.Select File/Print Setup from the Menu Bar.2.The Print Settings Dialog Box will be displayed. Make the settingsfor each item.SettingExplanationProgram frame displayCheck this box to print the print frame.Parameter settingsinformationCheck this box to print the timer, counter,and other parameter settings.
Informationwill be printed only for portions of the memory areas that are being used.35Section 2-7Printing Ladder ProgramsSetting3.ExplanationPrint titleCheck this box to print the title.Drawing nameEnter the drawing name.Figure No.Enter the drawing number.Revision markEnter the revision mark.Prepared byEnter the name of the person who wrote theprogram.DateEnter the date the program was written.Click the OK Button to save the settings as the print settings forthe ZEN Support Software. Click the Cancel Button to discard thesettings.Note a) To specify whether I/O comments are to be printed, either click the Show Comments Button on the Toolbar orselect View(V)/Comments from the Menu Bar.b) To specify whether a ladder diagram or electrical circuitdiagram is to be printed, either click the Ladder rung diagram Button or the Electrical circuit diagram Buttonon the Toolbar or else select View(V)/Circuit display/Ladder rung diagram or Electrical circuit diagramfrom the Menu Bar.2-7-2Print Preview1,2,3...361.Click the Print Preview Button on the Toolbar or select File/PrintPreview from the Menu Bar to check the print layout.2.The Print Preview Screen will be displayed.Printing Ladder Programs2-7-3Section 2-7Printing1,2,3...1.Click the Print Button on the Toolbar or select File/Print from theMenu Bar.2.The Print Dialog Box will be displayed.
Make settings for eachitem and click the OK Button.37Printing Ladder Programs38Section 2-7SECTION 3Transferring and Monitoring ProgramsThis section describes how to connect to the ZEN and how to transfer programs between the ZENand the ZEN Support Software.3-1Connecting the ZEN and Communications Settings . . . .
. . . . . . . . . . . . . . . 403-1-1Connecting to the ZEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 403-23-33-43-53-63-7Connecting Online . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Transferring Programs to the ZEN. . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .Transferring Programs from the ZEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Verifying Programs with ZEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Operating and Stopping the ZEN. .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Monitoring Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-7-1Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . .3-1-23-83-9Communications Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41424344454646463-7-2Displaying Present Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 473-7-3Changing Settings Online . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . 47Setting and Resetting Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Clearing Errors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4939Connecting the ZEN and Communications Settings3-13-1-1Section 3-1Connecting the ZEN and CommunicationsSettingsConnecting to the ZENUse a ZEN-CIF01 Computer Connecting Cable to connect the ZENand a serial port (COM port) of the computer.ZEN-CIF01 ComputerConnecting CableNote The connector on the computer side of the ZEN-CIF01 ComputerConnecting Cable is a 9-pin D-sub connector. If the computer hasa 25-pin D-sub connector, use a commercially available conversion connector or conversion cable.For 9-pin D-sub Serial Port ConnectorsZEN-CIF01 ComputerConnecting CableFor 25-pin D-sub Serial Port ConnectorsZEN-CIF01 ComputerConnecting CableConversion connector40Section 3-1Connecting the ZEN and Communications Settings3-1-2Communications SettingsCommunications settings must be made in the ZEN Support Software before commencing communications with the ZEN.1,2,3...1.Select File/Communications Settings from the Menu Bar.2.The Communications Settings Dialog Box will be displayed.
Makethe settings for each item.SettingDetailsDefaultModemNoneSet to “None.” The port specifiedunder Port name will be connectedto the ZEN.Local information(See note b.)This is the local information set onthe computer.---Country code(See note b.)The connection destination country code.---Area code(See note b.)The connection destination areacode.---Telephone No.(See note b.)The connection destination telephone number.---Port nameSelect either COM1 or COM 2.COM 1Node No.(See note a.)Specify a node number between 0and 9.0Monitor timeSpecify the communications moni- 2tor time between 0 and 30 s.Note a) Set the same node number as set on the ZEN.
Communications cannot be performed if the node numbers aredifferent.b) Do not make any settings for these items. These settings are for function expansion.3.Click the OK Button to save the settings in the project.Click the Cancel Button to discard the settings.Click the Defaults Button to return to the default settings.41Section 3-2Connecting Online3-2Connecting OnlineCheck communications with the ZEN before transferring or verifyingprograms. Connect the ZEN and perform the check operation withthe project file open.1,2,3...1.Select File/Properties from the Menu Bar and make the ZENmodel and Expansion I/O Units 1 to 3 settings in the PropertiesDialog Box to match the system configuration of the ZEN to beconnected online.2.Click the Go Online Button on the Toolbar or select ZEN/Go Online from the Menu Bar.
A confirmation dialog box will be displayed. Click the OK Button.3.Check that the Status Bar display has changed from Offline to Online. The background color for the ladder view area will change togray when the ZEN is online.Click the Go Online Button on the Toolbar again or select ZEN/Go Online from the Menu Bar.
The display on the Status Bar willreturn from Online to Offline and the Ladder Program Screen willchange back to the normal background color.Note42a)Ladder programs cannot be edited when online. Always gooffline before creating or editing ladder programs.b)Select ZEN/ZEN Information from the Menu Bar while online to obtain information about the connected ZEN.Transferring Programs to the ZEN3-3Section 3-3Transferring Programs to the ZENThis section describes how to transfer ladder programs created usingthe ZEN Support Software to the ZEN.The ZEN must be connected and online and the project file openedbefore the program transfer operation can be executed.!Caution Check the safety of connected devices before transferring programs to the ZEN.
Injuries may occur if programs are transferredcarelessly.1,2,3...1.Click the Transfer to ZEN Button on the Toolbar or select ZEN/Transfer/Transfer to ZEN from the Menu Bar. The Transfer toZEN Dialog Box will be displayed. Click the OK Button to transferthe program to the ZEN. Click the Cancel Button to cancel thetransfer.Settings Details• Turn ON The settings are downloaded too in the Transfer to ZENDialog Box to download the ZEN settings in the ZEN SupportSoftware at the same time.Refer to 4-1 ZEN Settings for information on the various ZENsettings.• Turn ON Protection is set in the Transfer to ZEN Dialog Box if theZEN is to be protected by the password set in the ZEN SupportSoftware.
Leave this check box turned OFF if no password hasbeen set.Refer to 4-2 Setting a Password for information on setting passwords.Note Refer to 6-2 Program Check Errors and Warnings for informationon error messages that occur during transfer from the computerto the ZEN.43Transferring Programs from the ZEN3-4Section 3-4Transferring Programs from the ZENThis section describes how to transfer ZEN ladder programs to theZEN Support Software.The ZEN must be connected and online and the project file openedbefore the program transfer operation can be executed.1,2,3...1.Click the Transfer From ZEN Button on the Toolbar or selectZEN/Transfer/Transfer from ZEN from the Menu Bar. The Transfer From ZEN Dialog Box will be displayed.
Click the OK Button totransfer the program from the ZEN. Click the Cancel Button tocancel the transfer.Settings DetailsTurn ON The settings are uploaded too in the Transfer From ZENDialog Box to upload the ZEN settings at the same time.2.If the transfer from the ZEN to the computer has been completednormally, the set password will be cleared.
A confirmation boxconfirming the clearing of the password will be displayed. If nopassword had been set, this confirmation box will not be displayed.Note Refer to 6-2 Program Check Errors and Warnings for informationon error messages that occur during transfer from the ZEN to thecomputer.44Section 3-5Verifying Programs with ZEN3-5Verifying Programs with ZENThis section describes how to compare the programs in the ZEN andZEN Support Software to verify that they are the same.The ZEN must be connected and online and the project file openedbefore the program verification operation can be executed.1,2,3...1.Click the Compare with ZEN Button on the Toolbar or selectZEN/Transfer/Compare with ZEN from the Menu Bar.
The Compare With ZEN Dialog Box will be displayed. Click the OK Buttonto compare the ZEN and ZEN Support Software programs. Clickthe Cancel Button to cancel the verification.Settings DetailsTurn ON The settings are compared too in the Compare WithZEN Dialog Box to compare the ZEN and ZEN Support Softwaresettings at the same time.2.A confirmation dialog box will be displayed if the verification hasbeen completed normally.When Programs Are theSameWhen Programs AreDifferentNote Refer to 6-2 Program Check Errors and Warnings for informationon error messages that occur during verification.45Operating and Stopping the ZEN3-6Section 3-6Operating and Stopping the ZENThis section describes how to operate and stop the ZEN from theZEN Support Software.The ZEN must be connected and online and the project file openedbefore these operations can be executed.Note1,2,3...3-71.Check that the power supply and input and output circuits arewired correctly before starting operation.2.Remove the output wiring before performing operation tests forsystems that have loads connected to the output circuit that couldcause serious damage to persons or equipment if there is a malfunction.3.Always check safety in the vicinity of equipment before turningON the power or changing operation modes.1.Select ZEN/Change operating mode/RUN from the Menu Bar.2.Check that the Status Bar display changes from STOP to RUN.3.Select ZEN/Change operating mode/STOP from the Menu Barto stop ZEN operation.