NT21_Setup Manual (V068-E1-1) (986757), страница 4
Текст из файла (страница 4)
This operation is not normally necessary.*2: Display of the system menu, and all change operations, can be inhibited. Thisenables you to prevent the accidental deletion or alteration of screens andsettings.7SectionBefore OperatingReference:1-4S For the system program, use the NT21 system program supplied as an accessory with the NT-series Support Tool (NT-ZJCAT1-EV4.6).S For the NT Support Tool, use NT-series Support Tool for Windows (Ver. 4.6).Refer to the following manuals for the devices and software.Device or SoftwareManual TitleCat.
No.NT21NT31/NT31C,NT631/NT631CReference ManualV069-E1-jSystem InstallerNT-series Support Tool for Windows (Ver. 4.6) Operation ManualV061-E1-jNT Support ToolNT-series Support Tool for Windows (Ver. 4.6) Operation ManualV061-E1-jPCSYSMAC CPM1 Operation ManualW262-E1-jSYSMAC CPM1A Operation ManualW317-E1-jSYSMAC CPM2A Operation ManualW352-E1-jSYSMAC CPM2C Operation ManualW356-E1-jSYSMAC C200H Operation Manual (for CPU01/03/11) (Programming)W130-E1-jSYSMAC C200H Operation Manual (for CPU21/23/31) (Programming)W217-E1-jSYSMAC C200HS Installation GuideW236-E1-jSYSMAC C200HS Operation Manual (Programming)W235-E1-jSYSMAC C200HX/HG/HE (-Z) Installation GuideW302-E1-jSYSMAC C200HX/HG/HE Operation ManualW303-E1-jSYSMAC C200HX/HG/HE-Z Operation ManualW322-E1-jSYSMAC CQM1/CPM1/CPM1A/SRM1 Programming ManualW228-E1-jSYSMAC CQM1H Operation ManualW363-E1-jSYSMAC CVM1/CV500/CV1000/CV2000/CVM1 Operation Manual: Ladder DiagramsW202-E1-jCS Series Programmable Controllers Operation ManualW339-E1-jCJ Series CJ1G-CPUjj-E Programmable Controllers Operation ManualW393-E1-jCS/CJ Series Programming ManualW394-E1-jCS/CJ Series Serial Communications Boards/Units Operation ManualW336-E1-jSYSMAC CQM1H Series Serial Communications Board Operation ManualW365-E1-jCompoBus MasterControl UnitSRM1 (-V2) Operation ManualW318-E1-jProgramminggg ToolsSYSMAC Support Software Operation Manual: C-series PCsW248-E1-jSYSMAC Support Software Operation Manual: CVM1 PCsW249-E1-jSYSMAC CPT User Manual and Quick Start GuideW332-E1-jW333-E1-jCX-Programmer User ManualHost Link Unit/S i lCSerialCommunicaitions Board8-SYSMAC C Series Host Link Unit System ManualW143-E1-jSYSMAC CVM1/CV Series Host Link Operation ManualW205-E1-jSYSMAC C200HW-COM01 C200HW-COM02-V1 to C200HW-COM06-EV1 Communications Board Operation ManualW304-E1-jSECTION 2Preparing for ConnectionThis section describes the connection methods that are possible with the PTs, and the functions of the parts of PTs, as therequired knowledge before connecting to the host and to other devices.2-12-2Method for Connection to the Host .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Names and Functions of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10139SectionMethod for Connection to the Host2-12-1Method for Connection to the HostThis section describes the methods for connection to the host used with theNT21, and the relationship between the connection method and the communication method.NT21 Communication Ports and Communication MethodsThe NT21 has two communication ports. Their uses are indicated in the tablebelow.CommunicationPortUsable Communication MethodsSerial port AHost Link1:1 NT Link1:N NT Link*Memory Link(NT Support Tool connection)(Bar code reader input function)RS-232CSerial port BHost Link1:1 NT Link1:N NT Link*Memory LinkRS-232CCommunications* There are two 1:N NT Link communications rates: standard and high-speed.Communication Methods That Can Be Used with the HostThe following communication methods can be used with the hosts that can beconnected to the NT21.• RS-232C• RS-422A• RS-485The communications types that are actually supported vary with the host.
Fordetails, refer to Section 4 Connecting to the Host from the RS-232C Port andSection 5 Connecting to the Host from the RS-422A/485 Port.Converting Communication Type with the RS-232C/RS-422A Link AdapterAn OMRON NT-AL001-E or NS-AL002-E Link Adapter can be used convertfrom RS-232C communications to either RS-422A or RS-485.• RS-232C ⇔ RS-422A• RS-232C ⇔ RS-485There are two models of Link Adapters available with different features:• NT-AL001 Link AdapterThe RS-232C port is insulated from the RS-422A/485 terminals.
An RS-232Ccable (2 m max.) can be connected to either serial port A or B on the NT21.• NS-AL002 Link AdapterThe RS-232C port is not insulated from the RS-422A/485 terminals. The NSAL002 Link Adapter can be connected directly to serial port B on the NT21.(The NS-AL002 cannot be connected directly to serial port A on the NT21.)10SectionMethod for Connection to the Host2-1Combinations of Communication Method and Connection MethodThe connection methods that can be used depending on the communicationmethod used and the communications type for communication between theNT21 and the host are indicated in the table below.Usable CommunicationMethodCommunicationtype at HostUsable Connection MethodDetailsHostLink1:1 NTLink1:NNTLinkMemorylinkffffDirect 1:1 connectionPTHostRS-232C63RS-232C (max.
15 m)1:N connection with RS-422A through Link AdaptersPTRS-232CNT-AL001* orNS-AL002Link AdapterNT-AL001Link AdapterRS-422A(total length 500 m)HostRS-232C(max. 2 m)f95f951:N connection with RS-485 through Link AdaptersPTRS-232CNT-AL001* orNS-AL002Link AdapterNT-AL001Link AdapterHostRS-485RS232C(total length 500 m) (max.
2 m)f: Connection possible: Connection not possibleNote *An RS-232C Cable (not shown in the diagram) is required when connecting anNT-AL001 Link Adapter to a PT.11SectionMethod for Connection to the HostCommunicationtype at HostUsable Communication MethodUsable Connection MethodHostLink1:1 NTLink1:N NTLinkMemorylinkffff2-1DetailsDirect 1:1 connection with RS-422A through a LinkAdapterRS-422APTNT-AL001* orNS-AL002Link AdapterHost85RS-422A (max.
500 m)Direct 1:1 connection with RS-485 through a LinkAdapterRS-485PTNT-AL001* orNS-AL002Link AdapterHostf88f89f92RS-485 (max. 500 m)1:N connection with RS-422A through Link AdaptersPTNT-AL001* orNS-AL002Link AdapterHostRS-422A (total length 500 m)RS-422A1:N connection with RS-485 through Link AdaptersPTRS-485NT-AL001* orNS-AL002Link AdapterHostRS-485 (total length 500 m)f: Connection possible: Connection not possibleNote *An RS-232C Cable (not shown in the diagram) is required when connecting anNT-AL001 Link Adapter to a PT.• The NT-AL001 Link Adapter requires a +5-V, 150 mA power supply at pin 6 ofthe RS-232C connector. When the NT-AL001 is being connected to the NT21,a 5-V power supply is output from pin 6 of serial port A or B in the NT21.
Connect pin 6 of the Link Adapter’s RS-232C connector with pin 6 of the NT21’sRS-232C connector.When the NT-AL001 is being connected to a host and power is not suppliedfrom the host’s port, connect an external power supply to pins 6 and 9 of theLink Adapter’s RS-232C connector. Connect the +5-V line to pin 6 and the SGline to pin 9.• Never connect or disconnect cables or Units to an NT-AL001 or NS-AL002while the power is ON. Be sure to turn OFF the power supply of the NT21 orhost before connecting or disconnecting the cables.• A +5-V power supply is output from pin 6 of serial ports A and B in the NT21. It ispossible to use the power from both ports simultaneously, but the maximumcapacity is 150 mA max.
total. Do not exceed 150 mA total output.• When using RS-422A or RS-485 communications, it is convenient to use anNS-AL002 Link Adapter and make a direct connection to serial port B of theNT21. However, there is no insulation between the NS-AL002’s RS-232C portand RS-422A/RS-485 port.12SectionNames and Functions of Parts2-22-2Names and Functions of PartsBefore starting operation, the names and functions of the parts of the NT21 aredescribed here as a confirmation. A method of hardware settings is also described.Front ViewDisplayMonochrome LCD screen with backlightRUN Indicator• Lit in green while theNT21 is in the RUNmode.The whole area of the screen is a touchpanel that works as an input device.• Lit in orange or red whenthe battery is low (orangein the RUN mode, red inother modes).Reference: The NT21 comes in two body colors.NT21Body ColorNT21-ST121-EBeigeNT21-ST121B-EBlack13SectionNames and Functions of Parts2-2Rear ViewExpansion interface connectorWhen using an Expansion Interface Unitsuch as a Memory Unit, connect it here.Battery coverThere is a battery holder beneath this cover.
Thebattery is optional (sold separately) and is notinstalled when the NT21 is shipped.Serial port B connectorConnect the cable for connection to thehost here. An NS-AL002 Link Adapter canbe connected directly to this port. This is a9-pin connector for RS-232C only.Power input terminalsConnect the power to theNT21 at these terminals.GR terminalGrounding terminal toprevent malfunctiondue to noise.Serial port A connectorConnect the cable for connection to the host or NT SupportTool here. A bar code reader can also be connected here.This is a 9-pin connector for RS-232C only.Note Before turning the power ON/OFF, confirm system safety, otherwise the systemmay operate unpredictably.14SECTION 3Hardware Installation and ConnectionsThis section describes the installation of the PTs and methods for connection to other devices.For details on connecting to the host, refer Section 4 Connecting to the Host from the RS-232C Port or Section 5 Connecting tothe Host from the RS-422A/485 Port.3-13-23-33-43-5Installation .