No response will be returned.(2) Response CodeNormal CompletionResponse code0000NameNormal completionDescriptionNo errors were found.Error OccurredResponse code2-14NameDescription1001Command too longThe command is too long.2203Operation errorEEPROM error2.3 Detailed Description of the Services■ Operation CommandThis service performs operations such as run/stop, communicationswriting, write mode, save RAM data, AT (auto-tuning) execution/cancel,multi-SP, move protect level, move to setup area 1, and software reset.Service Request PDUMRC SRC3 0 0 522Com- Relatedmand informacodetion22Service Response PDUMRC SRC Responsecode3 0 0 5224(1) Command Code and Related InformationCommandcodeCommand contentRelated Information00Communications writing00: OFF (disabled)01: ON (enabled)01RUN/STOP00: Run01: Stop02Multi-SP00: Set point 001: Set point 102: Set point 203: Set point 303AT execute/cancel00: Cancel01: AT execute04Write mode00: Backup01: RAM05Save RAM data0006Software reset (See note.)0007Move to setup area 10008Move to protect level0009Auto/manual switch00: Automatic mode01: Manual mode0BParameter initialization00: Initialize to defaults11Program start00: Reset01: StartNote: No response will be returned when a software reset is carried out.(2) Response CodeNormal CompletionResponse code0000NameNormal completionDescriptionNo errors were found.2-15SECTION 2 CompoWay/F Communications ProceduresError OccurredResponse codeError nameCause1001Command too longThe command is too long.1002Command too shortThe command is too short.1100Parameter errorCommand code and relatedinformation are wrong.2203Operation error• The “communications writing” parameter is set to“OFF” (disabled).
The command is received regardlessof the “communications writing” parameter setting (ON/OFF).• Processing could not be performed. For details, see (3)Operation Commands andPrecautions below.• EEPROM error(3) Operation Commands and Precautions● Communications WritingSet the “communications writing” parameter to “ON: enabled” or “OFF:disabled” with the related information setting. The setting can beaccepted in both setup area 0 and setup area 1.● RUN/STOPSet control to “run” or “stop” with the related information setting. Thesetting can be accepted in both setup area 0 and setup area 1.● Multi-SPSet four set points beforehand in the adjustment level so that you canswitch to a desired set point.
The setting can be accepted in both setuparea 0 and setup area 1.● AT Execute/CancelSet AT (auto-tuning) to “execute” or “cancel” with the related informationsetting. This command can be accepted in setup area 0 only. An“operation error” will be generated in the following instances:• When the “run/stop” parameter is set to “stop”• When the command is executed in “setup area 1”• When ON/OFF control is being used● Write ModeSet either the backup mode or RAM write mode with the related information setting. The setting can be accepted in both setup area 0 andsetup area 1.2-162.3 Detailed Description of the ServicesThe number of EEPROM (non-volatile memory) write operations islimited.
Therefore, use RAM write mode when frequently overwritingdata.Write modeDescriptionBackup modeThe data is written to EEPROM when the parameters in the operation/adjustment levels (excludingread-only parameters) are written by communications.RAM write modeThe data is not written to EEPROM when the parameters in the operation/adjustment levels (excludingread-only parameters) are written by communications.
Parameters can be changed by operating thekeys on the front panel of the controller.• When the mode is switched from RAM write mode to backup mode, theparameters in the operation/adjustment levels (excluding read-onlyparameters) are written to EEPROM.• The RAM write mode is enabled only when the “communicationswriting” parameter is set to “ON” (enabled).Consequently, when the “communications writing” parameter setting ischanged to “OFF” (disabled), the parameters in the operation/adjustment levels (excluding read-only parameters) are written toEEPROM even if the mode is set to RAM write mode.● Save RAM DataThis command writes the parameters in the operation/adjustment levels(excluding read-only parameters) to EEPROM.
The setting can beaccepted in both setup area 0 and setup area 1.● Software ResetRestarts processing from the point when power is turned ON. Thesetting can be accepted in both setup area 0 and setup area 1. Noresponse will be returned for this operation command.● Move to Setup Area 1This command moves to “setup area 1” and can be accepted at bothsetup areas 0 and 1. If the “initial setup/communications protection” isset to “2,” an “operation error” will be generated, and the move to setuparea 1 will be prohibited.When this move is carried out from setup area 0, the display indicatesthe “input type” in the “initial setting level.” When this operationcommand is executed in setup area 1, the display will not change.2-17SECTION 2 CompoWay/F Communications Procedures◆ Moving to Setup Area 1 in Manual ModeWhen this operation command is issued in manual mode, an“operation error” will be generated, and the move to setup area 1 willbe prohibited.● Move to Protect LevelThis command moves to the “protect level” and can be accepted only insetup area 0.When this command is issued in setup area 1, an“operation error” will be generated, and the move to the protect level willbe prohibited.◆ Moving to Protect Level in Manual ModeWhen this operation command is issued in manual mode, an“operation error” will be generated, and the move to the protect levelwill be prohibited.● Auto/Manual SwitchThis operation command switches the mode to manual mode orautomatic mode, based on the related information setting.
Thiscommand can be accepted in setup area 0 only. An “operation error”will be generated in the following instances:• When the command is executed in “setup area 1"• When auto/manual switching is disabled (not displayed)When the Controller is switched to manual mode, the “manual manipulated variable” will be displayed. When the Controller is switched frommanual mode to automatic mode, the operation level’s first parameterwill be displayed. When the Controller is switched to manual modewhile already in manual mode, the command will be completednormally and the display will not change (the contents will not berefreshed).◆ Writing Auto/Manual Status in EEPROMThe write mode determines whether the auto/manual status is writtento EEPROM.Write mode2-18DescriptionBackup modeWhen the auto/manual mode is switched bycommunications, the auto/manual status is written to EEPROM.RAM write modeWhen the auto/manual mode is switched bycommunications, the auto/manual status is notwritten to EEPROM.The status can be written with the Controllerkey operation.2.3 Detailed Description of the Services* When the auto/manual mode is switched with an operationcommand through communications and the Controller is in RAMwrite mode, the auto/manual status is not stored in EEPROM.Consequently, if the Controller is restar ted by performing asoftware reset or turning the power OFF and ON again, the auto/manual mode is set to the last saved status.◆ Switching to Manual Mode during Auto-tuningIf the mode is switched during auto-tuning (AT), the AT will becancelled and the Controller will be switched to manual mode.● Parameter InitializationThe present settings are returned to the default values and written toEEPROM.
This command can be accepted in setup area 1 only. Whenthis command is issued in setup area 0, an “operation error” will begenerated.The set values that are set during initialization depend on thecommand’s related information setting, as shown in the following table.Relatedinformation00Explanation (initialization values)Default initialization values (See SECTION 3 Communications Data for CompoWay/F and SYSWAY for details.)(These settings are the same as the ones used when“FACT” is selected for the setting data’s set value initialization.)● Program StartThe simple program function can be reset/started with the related information setting.
The setting can be accepted in both setup area 0 andsetup area 1. An operation error will be generated if program start hasbeen set in the event input.2-19SECTION 2 CompoWay/F Communications Procedures2.4 Response Code ListNormal CompletionResponsecode0000NameNormal completionErrordetectionpriorityDescriptionNo errors were found.NoneError OccurredResponsecodeNameErrordetectionpriorityDescription0401Unsupported commandThe service function for the relevant command isnot supported.11001Command too longThe command is too long.21002Command too shortThe command is too short.31101Area type errorWrong variable type41103Start address out-of-range errorThe read/write start address is out of range.51104End address out-of-range errorThe write end address (write start address +number of elements) exceeds the final addressof the variable area.61003Number of elements/data mismatchThe amount of data does not match the numberof elements.7110BResponse too longThe response exceeds the communicationsbuffer size (when the number of elements islarger than 0002).81100Parameter error• Bit position is not “00.”• The write data is out of the setting range.• The command code or related information inthe operation command is wrong.93003Read-only errorVariable type “C0” was written to.102203Operation error• The “communications writing” parameter is setto “OFF” (disabled).• Attempted to write to a parameter in setuparea 1 from setup area 0.• Attempted to write to a protect parameter fromother than the protect level.• Writing was carried out during AT execution.• Processing is not possible by operation command.• EEPROM error112-20SECTION 3Communications Data forCompoWay/F and SYSWAYThis s ecti on li sts the de tails of th e co mmun ica tions data i n theCompoWay/F and SYSWAY communications protocols.3.13.2Variable Area (Setting Range) List ...............................
3-2Status.......................................................................... 3-153-1SECTION 3 Communications Data for CompoWay/F and SYSWAY3.1 Variable Area (Setting Range) ListThe following table lists the variable areas. Items expressed in hexadecimal in the “Set (monitor) value”column are the setting range for CompoWay/F communications. The values in parentheses are theactual setting range. Use the values in parentheses as the setting range for SYSWAY communications.Com DataWhen there is a section reference for a setting item, refer to that reference for details.VariabletypeAddressC00000PVTemperature: Use the specified range for each sensor.Analog: Scaling lower limit −5% FS to Scalingupper limit +5% FSC00001Status (See note 1.)See 3.2 Status for details.C00002Internal set point(See note 1.)SP lower limit to SP upper limitC00003Heater current 1 valuemonitorH'00000000 to H'00000226 (0.0 to 55.0)C00004MV monitor (heating)Standard: H'FFFFFFCE to H'0000041A(−5.0 to 105.0)Heating and cooling: H'00000000 to H'0000041A(0.0 to 105.0)C00005MV monitor (cooling)H'00000000 to H'0000041A (0.0 to 105.0)C00006Heater current value 2monitorH'00000000 to H'00000226 (0.0 to 55.0)C00007Leakage current value 1monitorH'00000000 to H'00000226 (0.0 to 55.0)C00008Leakage current value 2monitorH'00000000 to H'00000226 (0.0 to 55.0)C00009Soak time remain monitorH'00000000 to H'0000270F (0 to 9999)3-2Parameter nameSetting (monitor) valueLevelOperating3.1 Variable Area (Setting Range) ListVariabletypeAddressParameter nameSetting (monitor) value0000Operation/adjustmentprotectH'00000000 (0): No restrictions in operation and adjustment levelsH'00000001 (1): Move to adjustment level is prohibited.H'00000002 (2): Display and change of only “PV” and“PV/SP” parameters is allowed.H'00000003 (3): Display of only “PV” and “PV/SP” parameters is allowed.C10001Initial setting/communications protectH'00000000 (0): Move to initial setting/communicationssetting level is allowed.