A personal computer or Programmable Terminal connected in HostSectionCPM2A Features and Functions1-1Link mode can be used for operations such as reading/writing data in the PC’sI/O memory or reading/changing the PC’s operating mode.1:1 Host Link Communications1:N Host Link CommunicationsCommandsCommandsB500-AL004Link AdapterResponsesCPM1-CIF01CPM2A (Peripheral port connection*)*An RS-232C Adapter is neededto connect to the Peripheral port.ResponsesNT-AL001CPM2A(RS-232C port connection)RS-232C/RS-422A Adapter(Up to 32 PCs can be connected.)The TXD(48) and RXD(47) instructions can be used in no-protocol mode to exchange data with standard serial devices. For example, data can be receivedfrom a bar code reader or transmitted to a serial printer.
The serial devices canbe connected to the RS-232C port or Peripheral port.No-protocolCommunicationsInputting data froma bar code readerOutputting data toa serial printerBar code readerSerial printerCPM2A(RS-232C port connection*)CPM2A(RS-232C port connection*)*An RS-232C Adapter is needed to connect to the Peripheral port.High-speed 1:1 NT LinkCommunicationsIn a 1:1 NT Link, an OMRON Programmable Terminal (PT) can be connecteddirectly to the CPM2A. The PT must be connected to the RS-232C port; it cannotbe connected to the Peripheral port.OMRON PTCPM2A(RS-232C port connection)One-to-one PC LinkA CPM2A can be linked directly to another CPM2A, CQM1, CPM1, CPM1A,CPM2C, SRM1(-V2), or a C200HS or C200HX/HG/HE PC.
The 1:1 PC Link al-5SectionCPM2A Features and Functions1-1lows automatic data link connections. The PC must be connected through theRS-232C port; it cannot be connected through the Peripheral port.CPM2A(RS-232C port connection)Expansion Memory UnitCPM2A(RS-232C port connection)The CPM1-EMU01-V1 Expansion Memory Unit is a program loader for smallsize or micro PLCs. Using the CPM1-EMU01-V1, simple on-site transfer of userprograms and data memory is possible with PLCs.UploadingDownloadingSYSMACEEPROM6SectionCPM2A Features and Functions1-11-1-2 Overview of CPM2A FunctionsMain functionInterruptsVariations/DetailsInterrupt inputs4 inputs, see note 1.Response time: 0.3 msInterval timer interrupts1 inputSet value: 0.5 to 319,968 msPrecision: 0.1 msHigh-speed countersHigh-speed counter1 input, see note 2.Differential phase mode (5 kHz)Pulse plus direction input mode (20 kHz)Up/down input mode (20 kHz)Increment mode (20 kHz)Interrupt inputs (counter mode)4 inputs, see note 1.Incrementing counter (2 kHz)Decrementing counter (2 kHz)Pulse outputsScheduled interruptsOne-shot interruptNo interruptCount-check interrupt(An interrupt can be generated when thecount equals the set value or the countlies within a preset range.)No interruptCount-up interrupt2 outputs:Single-phase pulse output without acceleration/deceleration (See note 3.)10 Hz to 10 kHz2 outputs:Variable duty ratio pulse output (See note 3.)0.1 to 999.9 Hz, duty ratio 0 to 100%Synchronized pulse control1 output:Pulse output with trapezoidal acceleration/deceleration (See note 3.)Pulse plus direction output, up/down pulse output, 10 Hz to 10 kHz1 point, see notes 2 and 3.Quick-response inputInput frequency range: 10 to 500 Hz, 20 Hz to 1 kHz, or 300 Hz to 20 kHzOutput frequency range: 10 Hz to 10 kHz4 inputs, see note 1.Analog settings2 controls (setting ranges: 0 to 200 BCD)Input time constantDetermines the input time constant for all inputs.
(Settings: 1, 2, 3, 5, 10, 20, 40, or 80 ms)Calendar/ClockShows the current year, month, day of the week, day of the month, hour, minute, andsecond.Analog I/O Unit functions (CPM1A-MAD01)Minimum input signal width: 50 µsExpansion Unit functionsTwo analog inputs: input range 0 to 10 V, 1 to 5 V, or 4 to 20 mAOne analog output: output range 0 to 10 V, –10 to 10 V, or 4 to 20 mATemperature Sensor Unit functionsThermocouple input (CPM1A-TS001/002; 2/4 input points):K: –200° to 1,300°C (–300° to 2,300°F)0.0° to 500.0°C (0.0° to 900.0°F)J: –100° to 850°C (–100° to 1,500°F)0.0° to 400.0°C (0.0° to 750.0°F)Platinum resistance thermometer input (CPM1A-TS101/102; 2/4 input points):Pt100: –200.0° to 650.0°C (–300.0° to 1,200.0°F)JPt100: –200.0° to 650.0°C (–300.0° to 1,200.0°F)CompoBus/S Slave functions (CPM1A-SRT21)Exchanges 8 input bits and 8 output bits of data with the Master Unit.Note1.
These four inputs are shared by interrupt inputs, interrupt inputs in countermode, and quick-response inputs, but each input can be used for only onepurpose.7SectionBasic System Configurations1-22. This input is shared by the high-speed counter and synchronized pulse control functions.3. This output is shared by the pulse output and synchronized pulse controlfunctions. These functions can be used with transistor outputs only.1-2Basic System Configurations1-2-1 Stand-alone CPU UnitCPU Unit with 20/30 I/O PointsCPU Unit with 40 I/O PointsNumber of I/O points20 I/O points(12 inputs and 8 outputs)Power supply100 to 240 VAC24 VDC30 I/O points(18 inputs and 12 outputs)100 to 240 VAC24 VDC40 I/O points(24 inputs and 16 outputs)100 to 240 VAC24 VDC60 I/O points(36 inputs and 24 outputs)100 to 240 VAC24 VDCCPU Unit with 60 I/O PointsInputs24 VDC24 VDC24 VDC24 VDC24 VDC24 VDC24 VDC24 VDC24 VDC24 VDC24 VDC24 VDC24 VDC24 VDC24 VDC24 VDCOutputsRelayRelaySinking TransistorSourcing TransistorRelayRelaySinking TransistorSourcing TransistorRelayRelaySinking TransistorSourcing TransistorRelayRelaySinking TransistorSourcing TransistorModelCPM2A-20CDR-ACPM2A-20CDR-DCPM2A-20CDT-DCPM2A-20CDT1-DCPM2A-30CDR-ACPM2A-30CDR-DCPM2A-30CDT-DCPM2A-30CDT1-DCPM2A-40CDR-ACPM2A-40CDR-DCPM2A-40CDT-DCPM2A-40CDT1-DCPM2A-60CDR-ACPM2A-60CDR-DCPM2A-60CDT-DCPM2A-60CDT1-D1-2-2 CPU Unit, Expansion Units, and Expansion I/O UnitsUp to 3 Expansion Units or Expansion I/O Units can be connected to the expansion connector with expansion I/O connecting cables.
(Only one Expansion Unitor Expansion I/O Unit can be connected if an NT-AL001 Adapter is connected tothe RS-232C port because the CPU Unit’s 5-VDC power supply is limited.)There are four types of Units available: Expansion I/O Units, an Analog I/O Unit,Temperature Sensor Units, and a CompoBus/S I/O Link Unit.Expansion connectorExpansion I/O Unit or Expansion Unit(Analog I/O Unit, Temperature SensorUnit, or CompoBus/S I/O Link Unit)Expansion I/O connecting cable8SectionBasic System Configurations1-2A PC with 120 I/O points (the maximum) can be assembled by connecting threeExpansion I/O Units to a CPU Unit with 60 I/O points.CPM2A-60CDR-A× 1 Unit(36 inputs, 24 outputs)+CPM1A-20EDR1× 3 Units = 72 inputs, 48 outputs(12 inputs, 8 outputs)A PC with 6 analog inputs and 3 analog outputs (the maximum) can be assembled by connecting three Analog I/O Units.
(Only one Analog I/O Unit can beconnected if an NT-AL001 Adapter is connected to the CPU Unit’s RS-232Cport.)A PC with up to 6 temperature inputs for input from thermocouples or platinumresistance thermometers can be assembled by connecting Temperature SensorUnits.CompoBus/S I/O Link Units (Slave Units) can be connected to a CPU Unit.
I/Odata (8 inputs and 8 outputs) is transferred between the CPU Unit and the areaallocated to the CompoBus/S Slave. (The I/O data exchanged with the Slave isinternal data; there are no external input or output terminals.)Note1. Different types of Expansion I/O Units or Expansion Units can be connectedat the same time. For example, an Expansion I/O Unit, an Analog I/O Unit,and a CompoBus/S I/O Link Unit can be connected to the CPU Unit.2. When an NT-AL001 Adapter is connected to the RS-232C port, only one Expansion Unit or Expansion I/O Unit can be connected to the CPU Unit because of power supply limitations.Expansion I/O Units20-point I/O UnitUnitExpansionI/O Units20 I/Opoints12 inputs8 outputs8-point Input UnitMax.
numberInputsof Units3 Units max.24 VDC(See note.)24 VDC8 inputs8 outputs8-point Output UnitOutputsModelRelaysCPM1A-20EDR1Sinking transistorsCPM1A-20EDT24 VDCSourcing transistorsCPM1A-20EDT124 VDC---------RelaysSinking TransistorsSourcing TransistorsCPM1A-8EDCPM1A-8ERCPM1A-8ETCPM1A-8ET1Note Only one Expansion I/O Unit can be connected if an NT-AL001 Adapter is connected to the CPU Unit’s RS-232C port.Expansion UnitsAnalog I/O UnitTemperature Sensor UnitCompoBus/S I/O Link Unit9SectionStructure and OperationUnitMax.
numberInputsof Units3 Units max.2 analog inputs(See note.)Analog I/O Unit2 analog inputs (2 words)1 analog output (1 word)Temperature ThermocoupleSensor Unitinputs3 Units max.(See note.)1 Unit max.(See note.)3 Units max.(See note.)1 Unit max.(See note.)3 Units max.(See note.)PlatinumresistancethermometerinputsCompoBus/S I/O Link Unit8 inputs and 8 outputsOutputs2 inputs (K, J)1-3Model1 analog outputCPM1A-MAD01---CPM1A-TS0014 inputs (K, J)CPM1A-TS0022 inputs (Pt100, JPt100)CPM1A-TS1014 inputs (Pt100, JPt100)CPM1A-TS1028 bits8 bits(Inputs from the Master.)(Outputs to the Master.)CPM1A-SRT21Note Only one Expansion Unit can be connected if an NT-AL001 Adapter is connected to the CPU Unit’s RS-232C port.1-3Structure and Operation1-3-1 CPU Unit StructureThe following diagram shows the internal structure of the CPU Unit.PC SetupProgramOutput circuitsExternalinputdevicesInput circuitsI/O memoryExternaloutputdevicesSettingsSettingsPeripheralportCommunicationsprocessingRS-232CportSettingsCommunications switchI/O MemoryThe program reads and writes data in this memory area during execution.