H135-E1-01 (986778), страница 13

Файл №986778 H135-E1-01 (Техническая документация) 13 страницаH135-E1-01 (986778) страница 132015-07-23СтудИзба
Просмтор этого файла доступен только зарегистрированным пользователям. Но у нас супер быстрая регистрация: достаточно только электронной почты!

Текст из файла (страница 13)

(Move to advancedfunction setting level is displayed.)H'00000001 (1): Move to initial setting/communications setting level is allowed. (Move to advancedfunction setting level is not displayed.)H'00000002 (2): Move to initial setting/communications setting level is prohibited.0504Setup change protectionH'00000000 (0): OFF (Changing of setup on controller display is allowed.)H'00000001 (1): ON (Changing of setup on controller displayis prohibited.)0508Move to protect levelH'FFFFF831 to H'0000270F (−1999 to 9999)050APassword to move toprotect levelH'FFFFF831 to H'0000270F (−1999 to 9999)(Can only be set. The monitor value is always H’00000000.)050CParameter mask enableH'00000000 (0): OFFH'00000001 (1): ONLevelProtect6-3SECTION 6 Communications Data for ModbusAddressParameter nameSetting (monitor) valueLevel0600Manual manipulated variableStandard: H'FFFFFFCE to H'0000041A (−5.0 to 105.0)Heating and cooling: H'FFFFFBE6 to H'0000041A (−105.0 to105.0)Operating0602Set pointSP lower limit to SP upper limit0608Heater current 1 valuemonitorH'00000000 to H'00000226 (0.0 to 55.0)060AMV monitor (heating)Standard: H'FFFFFFCE to H'0000041A (−5.0 to 105.0)Heating and cooling: H'00000000 to H'0000041A (0.0 to105.0)060CMV monitor (cooling)H'00000000 to H'0000041A (0.0 to 105.0)0700Cooling coefficientH'00000001 to H'0000270F (0.01 to 99.99)0708Dead bandH'FFFFF831 to H'0000270F(−199.9 to 999.9 for TC/Pt multi-input models)(−19.99 to 99.99 for Analog input models)070AManual reset valueH'00000000 to H'000003E8 (0.0 to 100.0)070CHysteresis (heating)H'00000001 to H'0000270F(0.1 to 999.9 for TC/Pt multi-input models)(0.01 to 99.99 for Analog input models)070EHysteresis (cooling)H'00000001 to H'0000270F(0.1 to 999.9 for TC/Pt multi-input models)(0.01 to 99.99 for Analog input models)0710Control period (heat)H'00000000 (0): 0.5H'00000001 to H'00000063 (1 to 99)0712Control period (cool)H'00000000 (0): 0.5H'00000001 to H'00000063 (1 to 99)0718SP ramp time unitH'00000000 (0): EU/secondH'00000001 (1): EU/minuteAdvancedfunctionsetting071ASP ramp set valueH'00000000 (0): OFFH'00000001 to H'0000270F (1 to 9999)Adjustment071EMV at stopStandard: H'FFFFFFCE to H'0000041A (−5.0 to 105.0)Heating and cooling: H'FFFFFBE6 to H'0000041A (−105.0 to105.0)0722MV at PV errorStandard: H'FFFFFFCE to H'0000041A (−5.0 to 105.0)Heating and cooling: H'FFFFFBE6to H'0000041A (−105.0 to105.0)072CLower-limit temperatureinput shift valueH'FFFFF831 to H'0000270F (−199.9 to 999.9)0730Upper-limit temperatureinput shift valueH'FFFFF831 to H'0000270F (−199.9 to 999.9)0734Heater current 1 valuemonitorH'00000000 to H'00000226 (0.0 to 55.0)Operating0736Heater burnout detection 1H'00000000 to H'000001F4 (0.0 to 50.0)Adjustment0738Leakage current value 1monitorH'00000000 to H'00000226 (0.0 to 55.0)Operating6-4AdjustmentInitial setting6.1 Variable Area (Setting Range) ListAddressParameter nameSetting (monitor) valueLevel073AHS alarm 1H'00000000 to H'000001F4 (0.0 to 50.0)Adjustment0746Temperature input shiftvalueH'FFFFF831 to H'0000270F (−199.9 to 999.9)0748Heater current value 2monitorH'00000000 to H'00000226 (0.0 to 55.0)Operating074AHeater burnout 2 detectionH'00000000 to H'000001F4 (0.0 to 50.0)Adjustment074CLeakage current value 2monitorH'00000000 to H'00000226 (0.0 to 55.0)Operating074EHS alarm 2H'00000000 to H'000001F4 (0.0 to 50.0)Adjustment0750Soak time remain monitorH'00000000 to H'0000270F (0 to 9999)Operating0752Soak timeH'00000001 to H'0000270F (1 to 9999)0754Wait bandH'00000000 (0): OFFH'00000001 to H'0000270F(0.1 to 999.9 for TC/Pt multi-input models)(0.01 to 99.99 for Analog input models)Adjustment6-5SECTION 6 Communications Data for ModbusAddressParameter nameSetting (monitor) valueLevel0800Input digital filterH'00000000 to H'0000270F (0.0 to 999.9)Advancedfunctionsetting0900Set point 0SP lower limit to SP upper limitAdjustment0904Alarm value 1H'FFFFF831 to H'0000270F (−1999 to 9999)Operating0906Upper-limit alarm 1H'FFFFF831 to H'0000270F (−1999 to 9999)0908Lower-limit alarm 1H'FFFFF831 to H'0000270F (−1999 to 9999)090AAlarm value 2H'FFFFF831 to H'0000270F (−1999 to 9999)090CUpper-limit alarm 2H'FFFFF831 to H'0000270F (−1999 to 9999)090ELower-limit alarm 2H'FFFFF831 to H'0000270F (−1999 to 9999)0910Alarm value 3(See note 2.)H'FFFFF831 to H'0000270F (−1999 to 9999)0912Upper-limit alarm value 3(See note 2.)H'FFFFF831 to H'0000270F (−1999 to 9999)0914Lower-limit alarm value 3(See note 2.)H'FFFFF831 to H'0000270F (−1999 to 9999)091CSet point 1SP lower limit to SP upper limit0938Set point 2SP lower limit to SP upper limit0954Set point 3SP lower limit to SP upper limit0A00Proportional bandH'00000001 to H'0000270F (0.1 to 999.9)0A02Integral timeH'00000000 to H'00000F9F (0 to 3999)0A04Derivative timeH'00000000 to H'00000F9F (0 to 3999) (Range when RT is“OFF.”)H'00000000 to H'0000270F (0.0 to 999.9) (Range when RT is“ON.”)0A0AMV upper limitStandard:0A0CMV lower limitStandard:6-6MV lower limit + 0.1 to H’0000041A (MV lowerlimit + 0.1 to 105.0)H’FFFFFFCE to MV upper limit − 0.1 (−5.0 to MVupper limit − 0.1)Heating and cooling: H'FFFFFBE6 to H'00000000 (−105.0to 0.0)Adjustment6.1 Variable Area (Setting Range) ListAddress0C00Parameter nameInput type (TC/Pt multiinput models) (See note.)Setting (monitor) valueH'00000000 (0):H'00000001 (1):H'00000002 (2):H'00000003 (3):H'00000004 (4):H'00000005 (5):H'00000006 (6):H'00000007 (7):H'00000008 (8):H'00000009 (9):H'0000000A (10):H'0000000B (11):H'0000000C (12):H'0000000D (13):H'0000000E (14):H'0000000F (15):H'00000010 (16):H'00000011 (17):H'00000012 (18):H'00000013 (19):0C00Pt (−200 to 850°C/−300 to 1500°F)Pt (−199.9 to 500.0°C/−199.9 to 900.0°F)Pt (0.0 to 100.0°C/0.0 to 210.0°F)JPt (−199.9 to 500.0°C/−199.9 to 900.0°F)JPt (0.0 to 100.0°C/0.0 to 210.0°F)LevelInitial settingK (−200 to 1300°C/−300 to 2300°F)K (−20.0 to 500.0°C/0.0 to 900.0°F)J (−100 to 850°C/−100 to 1500°F)J (−20.0 to 400.0°C/0.0 to 750.0°F)T (−200 to 400°C/−300 to 700°F)T (−199.9 to 400.0°C/−199.9 to 700.0°F)E (0 to 600°C/0 to 1100°F)L (−100 to 850°C/−100 to 1500°F)U (−200 to 400°C/−300 to 700°F)U (−199.9 to 400.0°C/−199.9 to 700.0°F)N (−200 to 1300°C/−300 to 2300°F)R (0 to 1700°C/0 to 3000°F)S (0 to 1700°C/0 to 3000°F)B (100 to 1800°C/300 to 3200°F)Infrared temperature sensor (K 140°F/60°C)Input type (TC/Pt multiinput models) (See note.)H'00000014 (20): Infrared temperature sensor(K 240°F/120°C)H'00000015 (21): Infrared temperature sensor(K 280°F/140°C)H'00000016 (22): Infrared temperature sensor(K 440°F/220°C)H'00000017 (23): 0 to 50 mVInput type (Analog inputmodels, see note)H'00000000 (0): 4 to 20 mAH'00000001 (1): 0 to 20 mAH'00000002 (2): 1 to 5 VH'00000003 (3): 0 to 5 VH'00000004 (4): 0 to 10 V0C02Temperature unitH'00000000 (0): °CH'00000001 (1): °F0C12Scaling lower limitH’FFFFF831 to scaling upper limit −1(−1999 to scaling upper limit −1)0C16Scaling upper limitScaling lower limit +1 to H’0000270F(Scaling lower limit +1 to 9999)0C18Decimal point position(TC/Pt multi-input models)H'00000000 to 00000001 (0 to 1)Decimal point position(Analog input models)H'00000000 to 00000003 (0 to 3)Initial settingNote 1.

The input type can be selected to match the connected sensor.There are two input type specifications: Thermocouple/Resistance thermometer input andAnalog input.Note 2. The alarm function can also be used in Controllers without alarm output terminals. In this case,confirm alarm occurrences via the status data.6-7SECTION 6 Communications Data for ModbusAddressParameter nameSetting (monitor) value0D06Linear current outputH'00000000 (0): 4 to 20 mAH'00000001 (1): 0 to 20 mA0D1ESP upper limitThe range of values (without decimal point) is as follows:Temperature: SP lower limit + 1 to Input range upper limitAnalog: SP lower limit + 1 to scaling upper limit0D20SP lower limitThe range of values (without decimal point) is as follows:Temperature: Input range lower limit to SP upper limit − 1Analog: Scaling lower limit to SP upper limit − 10D22Standard or Heating andcoolingH'00000000 (0): StandardH'00000001 (1): Heating and cooling0D24Direct/reverse operationH'00000000 (0): Reverse operationH'00000001 (1): Direct operation0D28PID/OnOffH'00000000 (0): ON/OFFH'00000001 (1): 2 degrees of freedom PID control0D2ASTH'00000000 (0): OFFH'00000001 (1): ON0D2CProgram patternH'00000000 (0): OFFH'00000001 (1): STOPH'00000002 (2): CONT0E00Transfer output typeH'00000000 (0): OFFH'00000001 (1): Set pointH'00000002 (2): Set point during SP rampH'00000003 (3): PVH'00000004 (4): MV monitor (heating)H'00000005 (5): MV monitor (cooling)0E0CControl output 1 assignmentWhen control output 1 is a linear output:H'00000000 (0): Not assigned.H'00000001 (1): Control output (heating)H'00000002 (2): Control output (cooling)When control output 1 is a pulse output:H'00000000 (0): Not assigned.H'00000001 (1): Control output (heating)H'00000002 (2): Control output (cooling)H'00000003 (3): Alarm 1H'00000004 (4): Alarm 2H'00000005 (5): Alarm 3H'00000006 (6): Program end output (See note 5.)0E0EControl output 2 assignmentH'00000000 (0): Not assigned.H'00000001 (1): Control output (heating)H'00000002 (2): Control output (cooling)H'00000003 (3): Alarm 1H'00000004 (4): Alarm 2H'00000005 (5): Alarm 3H'00000006 (6): Program end output (See note 5.)0E14Event input assignment 1H'00000000 (0): NoneH'00000001 (1): RUN/STOP (Cannot be set if the “Numberof multi-SP uses” is set to 1 or 2.)6-8LevelInitial settingAdvancedfunctionsetting6.1 Variable Area (Setting Range) ListAddressParameter nameSetting (monitor) valueLevel0E14Event input assignment 1H'00000002 (2): Auto/Manual (Cannot be set if the “Numberof multi-SP uses” is set to 1 or 2.)H'00000003 (3): Program Start (Cannot be set if the “Number of multi-SP uses” is set to 1 or 2.) (Seenote 6.)Advancedfunctionsetting0E16Event input assignment 2H'00000000 (0): NoneH'00000001 (1): RUN/STOP (Cannot be set if the “Numberof multi-SP uses” is set to 2.)H'00000002 (2): Auto/Manual (Cannot be set if the “Numberof multi-SP uses” is set to 2.)H'00000003 (3): Program Start (Cannot be set if the “Number of multi-SP uses” is set to 2.) (See note6.)0E20Alarm 1 assignmentH’00000000 to H’00000006 (0 to 6) (Same settings as thecontrol output 2 assignments)0E22Alarm 2 assignmentH’00000000 to H’00000006 (0 to 6) (Same settings as thecontrol output 2 assignments)0E24Alarm 3 assignmentH’00000000 to H’00000006 (0 to 6) (Same settings as thecontrol output 2 assignments)0E28Transfer output upperlimitH'FFFFF831 to H'0000270F (−1999 to 9999) (See note 4.)0E2ATransfer output lowerlimitH'FFFFF831 to H'0000270F (−1999 to 9999) (See note 4.)Initial setting6-9SECTION 6 Communications Data for ModbusAddressParameter nameSetting (monitor) valueLevel0F00Alarm 1 typeH'00000000 (0):H'00000001 (1):H'00000002 (2):H'00000003 (3):H'00000004 (4):H'00000005 (5):Alarm function OFFUpper and lower-limit alarmUpper-limit alarmLower-limit alarmUpper and lower-limit range alarmUpper and lower-limit alarm with standbysequenceH'00000006 (6): Upper-limit alarm with standby sequenceH'00000007 (7): Lower-limit alarm with standby sequenceH'00000008 (8): Absolute-value upper-limit alarmH'00000009 (9): Absolute-value lower-limit alarmH'0000000A (10): Absolute-value upper-limit alarm withstandby sequenceH'0000000B (11): Absolute-value lower-limit alarm withstandby sequenceH'0000000C (12): LBA (Loop Burnout Alarm)Initial setting0F02Alarm 1 latchH'00000000 (0): OFFH'00000001 (1): ON0F04Alarm 1 hysteresisH'00000001 to H'0000270F(0.1 to 999.9 for TC/Pt multi-input models)(0.01 to 99.99 for Analog input models)Advancedfunctionsetting0F06Alarm 2 typeH'00000000 (0):H'00000001 (1):H'00000002 (2):H'00000003 (3):H'00000004 (4):H'00000005 (5):Alarm function OFFUpper and lower-limit alarmUpper-limit alarmLower-limit alarmUpper and lower-limit range alarmUpper and lower-limit alarm with standbysequenceH'00000006 (6): Upper-limit alarm with standby sequenceH'00000007 (7): Lower-limit alarm with standby sequenceH'00000008 (8): Absolute-value upper-limit alarmH'00000009 (9): Absolute-value lower-limit alarmH'0000000A (10): Absolute-value upper-limit alarm withstandby sequenceH'0000000B (11): Absolute-value lower-limit alarm withstandby sequenceInitial setting0F08Alarm 2 latchH'00000000 (0): OFFH'00000001 (1): ON0F0AAlarm 2 hysteresisH'00000001 to H'0000270F(0.1 to 999.9 for TC/Pt multi-input models)(0.01 to 99.99 for Analog input models)Advancedfunctionsetting0F0CAlarm 3 type(See note 2.)Same settings as the alarm 2 type.6-10Initial setting6.1 Variable Area (Setting Range) ListAddressParameter nameSetting (monitor) value0F0EAlarm 3 latch(See note 2.)H'00000000 (0): OFFH'00000001 (1): ON0F10Alarm 3 hysteresis(See note 2.)H'00000001 to H'0000270F(0.1 to 999.9 for TC/Pt multi-input models)(0.01 to 99.99 for Analog input models)0F18Standby sequence resetH'00000000 (0): Condition AH'00000001 (1): Condition B0F1AAlarm 1 open in alarmH'00000000 (0): Close in alarmH'00000001 (1): Open in alarm0F1CAlarm 2 open in alarmH'00000000 (0): Close in alarmH'00000001 (1): Open in alarm0F1EAlarm 3 open in alarm(See note 2.)H'00000000 (0): Close in alarmH'00000001 (1): Open in alarm0F22Alarm 1 ON delayH'00000000 to H'000003E7 (0 to 999)0F24Alarm 2 ON delayH'00000000 to H'000003E7 (0 to 999)0F26Alarm 3 ON delay(See note 2.)H'00000000 to H'000003E7 (0 to 999)0F2AAlarm 1 OFF delayH'00000000 to H'000003E7 (0 to 999)0F2CAlarm 2 OFF delayH'00000000 to H'000003E7 (0 to 999)0F2EAlarm 3 OFF delay(See note 2.)H'00000000 to H'000003E7 (0 to 999)LevelAdvancedfunctionsetting6-11SECTION 6 Communications Data for ModbusAddressParameter nameSetting (monitor) value1006Automatic display returntimeH'00000000 (0): OFFH'00000001 to H'00000063 (1 to 99)1010Additional PV displayH'00000000 (0): OFFH'00000001 (1): ON1016MV displayH'00000000 (0): OFF (display of manipulated variable OFF)H'00000001 (1): ON (display of manipulated variable ON)1018Protect level move timeH'00000001 to H'0000001E (1 to 30)101APV change colorH'00000000 (0): ORGH'00000001 (1): REDH'00000002 (2): GRNH'00000003 (3): R-GH'00000004 (4): G-RH'00000005 (5): R-G.RH'00000006 (6): G-O.RH'00000007 (7): O-G.R101CPV stable bandH'00000001 to H'0000270F(0.1 to 999.9 for TC/Pt multi-input models)(0.01 to 99.99 for Analog input models)101EAdditional auto/manualdisplay switchH'00000000 (0): OFFH'00000001 (1): ON1020Display character switchH'00000000 (0): OFFH'00000001 (1): ON1100Protocol setting(See note 3.)H'00000000 (0): CompoWay/F (SYSWAY)H'00000001 (1): Modbus1102Communications unitnumber (See note 3.)H'00000000 to H'00000063 (0 to 99)1104Communications baudrate (See note 3.)H'00000000 (0): 1.2H'00000001 (1): 2.4H'00000002 (2): 4.8H'00000003 (3): 9.6H'00000004 (4): 19.2H'00000005 (5): 38.41106Communications datalength (See note 3.)H'00000007 (7): 7H'00000008 (8): 81108Communications stopbits (See note 3.)H'00000001 (1): 1H'00000002 (2): 2110ACommunications parity(See note 3.)H'00000000 (0): NoneH'00000001 (1): EvenH'00000002 (2): Odd110CSend data wait time(See note 3.)H'00000000 to H'00000063 (0 to 99)6-12LevelAdvancedfunctionsettingCommunicationssetting6.1 Variable Area (Setting Range) ListAddressParameter nameSetting (monitor) value130ACold junction compensation methodH'00000000 (0): OFFH'00000001 (1): ON1314αH'00000000 to H'00000064 (0.00 to 1.00)1328Heater burnout latchH'00000000 (0): OFFH'00000001 (1): ON132AHeater burnout hysteresisH'00000001 to H'000001F4 (0.1 to 50.0)132CHS alarm latchH'00000000 (0): OFFH'00000001 (1): ON132EHS alarm hysteresisH'00000001 to H'000001F4 (0.1 to 50.0)1334Number of multi-SP usesH'00000000 (0): No multi-SPH'00000001 (1): 2SPH'00000002 (2): 4SP1336Multi-SP usageH'00000000 (0): OFFH'00000001 (1): ON1338HB ON/OFFH'00000000 (0): OFFH'00000001 (1): ON133AMB command logicswitching (See note 7.)H'00000000 (0): OFFH'00000001 (1): ON133CInput error outputH'00000000 (0): OFFH'00000001 (1): ON133EInput shift typeH'00000000 (0): Temperature input 1-point shiftH'00000001 (1): Temperature input 2-point shift1340MV at stop and erroradditionH'00000000 (0): OFFH'00000001 (1): ON1342ST stable rangeH'00000001 to H'0000270F (0.1 to 999.9)1344RTH'00000000 (0): OFFH'00000001 (1): ON1346HS alarmH'00000000 (0): OFFH'00000001 (1): ON1348LBA detection timeH'00000000 to H'0000270F (0 to 9999)134ALBA levelH'00000001 to H'0000270F(0.1 to 999.9 for TC/Pt multi-input models)(0.01 to 99.99 for Analog input models)134CLBA bandH'00000000 to H'0000270F(0.0 to 999.9 for TC/Pt multi-input models)(0.00 to 99.99 for Analog input models)134ESoak time unitsH'00000000 (0): MinutesH'00000001 (1): Hours1350Alarm SP selectionH'00000000 (0): Set point during SP rampH'00000001 (1): Set pointLevelAdvancedfunctionsettingAdvancedfunctionsettingNote 1.Not displayed on the Controller display.Note 2.The parameter will not be shown on the Controller display when alarm 3 is not assigned to anoutput.Note 3.After communications parameters have been changed, they are enabled by resetting theController.6-13SECTION 6 Communications Data for ModbusNote 4.The setting (monitor) range depends on the “transfer output type” setting.

Характеристики

Тип файла
PDF-файл
Размер
1,1 Mb
Тип материала
Высшее учебное заведение

Список файлов учебной работы

Свежие статьи
Популярно сейчас
Зачем заказывать выполнение своего задания, если оно уже было выполнено много много раз? Его можно просто купить или даже скачать бесплатно на СтудИзбе. Найдите нужный учебный материал у нас!
Ответы на популярные вопросы
Да! Наши авторы собирают и выкладывают те работы, которые сдаются в Вашем учебном заведении ежегодно и уже проверены преподавателями.
Да! У нас любой человек может выложить любую учебную работу и зарабатывать на её продажах! Но каждый учебный материал публикуется только после тщательной проверки администрацией.
Вернём деньги! А если быть более точными, то автору даётся немного времени на исправление, а если не исправит или выйдет время, то вернём деньги в полном объёме!
Да! На равне с готовыми студенческими работами у нас продаются услуги. Цены на услуги видны сразу, то есть Вам нужно только указать параметры и сразу можно оплачивать.
Отзывы студентов
Ставлю 10/10
Все нравится, очень удобный сайт, помогает в учебе. Кроме этого, можно заработать самому, выставляя готовые учебные материалы на продажу здесь. Рейтинги и отзывы на преподавателей очень помогают сориентироваться в начале нового семестра. Спасибо за такую функцию. Ставлю максимальную оценку.
Лучшая платформа для успешной сдачи сессии
Познакомился со СтудИзбой благодаря своему другу, очень нравится интерфейс, количество доступных файлов, цена, в общем, все прекрасно. Даже сам продаю какие-то свои работы.
Студизба ван лав ❤
Очень офигенный сайт для студентов. Много полезных учебных материалов. Пользуюсь студизбой с октября 2021 года. Серьёзных нареканий нет. Хотелось бы, что бы ввели подписочную модель и сделали материалы дешевле 300 рублей в рамках подписки бесплатными.
Отличный сайт
Лично меня всё устраивает - и покупка, и продажа; и цены, и возможность предпросмотра куска файла, и обилие бесплатных файлов (в подборках по авторам, читай, ВУЗам и факультетам). Есть определённые баги, но всё решаемо, да и администраторы реагируют в течение суток.
Маленький отзыв о большом помощнике!
Студизба спасает в те моменты, когда сроки горят, а работ накопилось достаточно. Довольно удобный сайт с простой навигацией и огромным количеством материалов.
Студ. Изба как крупнейший сборник работ для студентов
Тут дофига бывает всего полезного. Печально, что бывают предметы по которым даже одного бесплатного решения нет, но это скорее вопрос к студентам. В остальном всё здорово.
Спасательный островок
Если уже не успеваешь разобраться или застрял на каком-то задание поможет тебе быстро и недорого решить твою проблему.
Всё и так отлично
Всё очень удобно. Особенно круто, что есть система бонусов и можно выводить остатки денег. Очень много качественных бесплатных файлов.
Отзыв о системе "Студизба"
Отличная платформа для распространения работ, востребованных студентами. Хорошо налаженная и качественная работа сайта, огромная база заданий и аудитория.
Отличный помощник
Отличный сайт с кучей полезных файлов, позволяющий найти много методичек / учебников / отзывов о вузах и преподователях.
Отлично помогает студентам в любой момент для решения трудных и незамедлительных задач
Хотелось бы больше конкретной информации о преподавателях. А так в принципе хороший сайт, всегда им пользуюсь и ни разу не было желания прекратить. Хороший сайт для помощи студентам, удобный и приятный интерфейс. Из недостатков можно выделить только отсутствия небольшого количества файлов.
Спасибо за шикарный сайт
Великолепный сайт на котором студент за не большие деньги может найти помощь с дз, проектами курсовыми, лабораторными, а также узнать отзывы на преподавателей и бесплатно скачать пособия.
Популярные преподаватели
Добавляйте материалы
и зарабатывайте!
Продажи идут автоматически
7034
Авторов
на СтудИзбе
260
Средний доход
с одного платного файла
Обучение Подробнее