Solid State Relays (Single-phase)G3PBNew Single-phase Solid State Relays withCompact Size for Heater Control• Slim models with a thickness of only 22.5 mm are also available.• Compact design achieved by optimizing heat sink shape.• DIN track mounting possible in addition to screw mounting.• Comply with EN60947-4-3 (IEC947-4-3) UL508, andCSA22.2 No. 14, and bear CE marking.Model Number Structure■ Model Number LegendG3PB-@@@-@@-@12 3 45 67SSR1. Basic Model NameG3PB:Solid State Relay2.
Rated Load Power Supply Voltage2:200 VAC3. Rated Load Current15:15 A25:25 A35:35 A45:45 A4. Terminal TypeB:Screw terminals5. Single-phase/3-phase and Number of Elements for 3-phaseBlank:Single-phase models6. Single-phase TypeBlank:DIN track mounting and built-in heat sink7. CertificationVD:Certified by UL, CSA, and VDESolid State Relays (Single-phase)G3PBJ-37Ordering Information■ List of ModelsIsolation methodPhototriac couplerZero crossfunctionYesOperationindicatorYes (yellow)Rated inputvoltage12 to 24 VDCRated output loadModel number15 A, 100 to 240 VACG3PB-215B-VD 12 to 24 VDC25 A, 100 to 240 VACG3PB-225B-VD 12 to 24 VDC35 A, 100 to 240 VACG3PB-235B-VD 12 to 24 VDC45 A, 100 to 240 VACG3PB-245B-VD 12 to 24 VDCNote: When ordering, specify the rated input voltage.■ Accessories (Order Separately)Mounting Track50 cm (1) x 7.3 mm (t)PFP-50N1 m (1) x 7.3 mm (t)PFP-100N1 m (1) x 16 mm (t)PFP-100N2Specifications■ Ratings (at an Ambient Temperature of 25°C)InputItemCommonRated voltage12 to 24 VDCOperating voltage range9.6 to 30 VDCRated input current7 mA max.Must operate voltage9.6 VDC max.Must release voltage1 VDC min.Insulation methodPhototriacOperation indicatorYellow LEDOutputItemG3PB-215B-VDG3PB-225B-VDG3PB-235B-VDRated load voltage100 to 240 VACLoad voltage range75 to 264 VACApplicable load current (See note.)0.1 to 15 A0.1 to 25 A0.5 to 35 AInrush current resistance (peak value)150 A(60 Hz, 1 cycle)220 A(60 Hz, 1 cycle)440 A(60 Hz, 1 cycle)Permissible I2t(half 60-Hz wave)260 A2s260 A2s2,660 A2sApplicable load(with Class-1 AC resistive load)3 kW max.(at 200 VAC)5 kW max.(at 200 VAC)7 kW max.(at 200 VAC)G3PB-245B-VD0.5 to 45 A9 kW max.(at 200 VAC)Note: The applicable load current varies depending on the ambient temperature.
For details, refer to Load Current vs. Ambient Temperature inEngineering Data.J-38Solid State Relays (Single-phase) G3PB■ CharacteristicsItemG3PB-215B-VDG3PB-225B-VDG3PB-235B-VDG3PB-245B-VDOperate time1/2 of load power source cycle + 1 ms max. (DC input)Release time1/2 of load power source cycle + 1 ms max. (DC input)Output ON voltage drop1.6 V (RMS) max.Leakage current10 mA max.
(at 200 VAC)Insulation resistance100 MΩ min. (at 500 VDC)Dielectric strength2,500 VAC, 50/60 Hz for 1 minVibration resistanceDestruction: 10 to 55 to 10 Hz, 0.375-mm single amplitude (Mounted to DIN track)Shock resistanceDestruction: 294 m/s2 (DIN track mounting)Ambient temperatureOperating:Storage:Ambient humidityOperating: 45% to 85%Certified standardsUL508 File No. E64562CSA22.2 No. 14 File No. LR35535IEC947-4-3 File No. 6825 UGWeightApprox.
240 g–30°C to 80°C (with no icing or condensation)–30°C to 100°C (with no icing or condensation)Approx. 400 gApprox. 400 gSSRApprox. 240 gSolid State Relays (Single-phase)G3PBJ-39Engineering DataG3PB-215B-VDG3PB-225B-VDG3PB-235B-VDG3PB-245B-VDLoad current (A)Load current (A)Load Current vs. Ambient TemperatureG3PB-225B-VDG3PB-245B-VDG3PB-235B-VDG3PB-215B-VDAmbient temperature (°C)Ambient temperature (°C)Close Mounting (3 Relays, 8 Relays)G3PB-225B-VDLoad current (A)Load current (A)G3PB-215B-VD3 Relays3 Relays8 Relays8 RelaysAmbient temperature (°C)Ambient temperature (°C)G3PB-245B-VDLoad current (A)Load current (A)G3PB-235B-VD3 Relays8 RelaysAmbient temperature (°C)Close Mounting ExampleDIN trackJ-40Solid State Relays (Single-phase) G3PB3 Relays8 RelaysAmbient temperature (°C)Input impedance (kΩ)Input current (mA)Input Voltage vs. Input Current and Input Voltage vs.
Input ImpedanceInput currentInput impedanceInput voltage (V)One Cycle Surge Current: Non-repetitiveNote: Keep the inrush current to half the rated value if it occurs repetitively.G3PB-225B-VDG3PB-235B-VDG3PB-245B-VDEnergized time (ms)Energized time (ms)SSREnergized time (ms)Inrush currentInrush currentInrush currentG3PB-215B-VDSolid State Relays (Single-phase)G3PBJ-41DimensionsNote: All units are in millimeters unless otherwise indicated.G3PB-215B-VDG3PB-225B-VDTwo, 4.6 dia.Two, M468100 max. 90±0.2 8024Two, M3.54.513±0.24.26.3Elliptical hole: 4.6 x 5.622.5 max.Note: Without terminal cover.Terminal Arrangement/Internal Circuit DiagramNote: With terminal cover.Mounting Holes(+)113±0.3Input side90±0.3Input circuit88.683.2Trigger circuit100 max.Output sideA1A22Three, 4.5 dia.
or M4G3PB-235B-VDG3PB-245B-VD)−(4.6 dia.Two, M568100 max. 90±0.2 8024Two, M3.513.46.1Elliptical hole: 4.6 x 5.64.525±0.244.5 max.Note: Without terminal cover.Terminal Arrangement/Internal Circuit DiagramNote: With terminal cover.Mounting Holes125±0.3(+)90±0.3A2Two, 4.5 dia.
or M4J-42Solid State Relays (Single-phase) G3PB2)−(Input side88.6Input circuit83.2Trigger circuit100 max.Output sideA1Accessories (Order Separately)Mounting TracksPFP-100N, PFP-50NPFP-100N2167.3±0.154.535±0.315 25 10 252525101,000 (500)(see note)4.527±0.1515 (5)(see note)35±0.3 27 2415 251025251,0001025 15129.21.5SSRNote: Values in parentheses indicate dimensions for thePFP-50N.Solid State Relays (Single-phase)G3PBJ-43Safety PrecautionsRelationship between SSRs and DuctsCountermeasure 1Mounting surfaceVertical mountingVertical MountingG3PBVerticaldirection→Duct orairflowobstructionMounting MethodCountermeasure 250 mm max.(A height of no morethan halfthe SSR'sheight isrecommended)G3PBG3PBAirflowMounting surfaceDuct HeightPlease observe the following precautions to prevent failure tooperate, malfunction, or undesirable effect on product performance.Mounting surface■ Precautions for Correct UseDuct orairflowobstructionPanelDo not surround the SSRwith ducts, otherwisethe heat radiation of theSSR will be adverselyaffected.Horizontal MountingUse short ducts.If the ducts cannot beshortened, place theSSR on a metalbase so that it is notsurrounded by theducts.VentilationBe aware of air flowDuct or air flowobstructionPanelNote: Make sure that the load current is 50% of the rated load currentwhen the G3PB is mounted horizontally.VentilationoutletG3PBG3PBG3PBClose MountingAir inletSSR Mounting PitchIf the air inlet or air outlet has a filter, clean the filter regularly toprevent it from clogging and ensure an efficient flow of air.Panel MountingBetween duct orairflowobstructionand SSRDuct or airflow obstructionSSR60 mm min.Mounting directionHost andslaveVertical direction30 mm min.80 mm min.Closemounting10 mm min.Do not locate any objects around the air inlet or air outlet, otherwisethe objects may obstruct the proper ventilation of the control panel.A heat exchanger, if used, should be located in front of the SSR Unitsto ensure the efficiency of the heat exchanger.Please reduce the ambient temperature of SSRs.The rated load current of an SSR is measured at an ambienttemperature of 25 or 40 °C.An SSR uses a semiconductor in the output element.
This causesthe temperature inside the control panel to increase due to heatingresulting from the passage of electrical current through the load. Torestrict heating, attach a fan to the ventilation outlet or air inlet of thecontrol panel to ventilate the panel. This will reduce the ambienttemperature of the SSRs and thus increase reliability. (Generally,each 10 °C reduction in temperature will double the expected life.)Load current (A)15 ARequired number of fans 0.23per SSR25 A0.3935 A0.5445 A0.70Example: For 10 SSRs with load currents of 20 A,0.23 x 10 = 2.3Thus, 3 fans would be required.Size of fans: 92 mm2, Air volume: 0.7 m3/min,Ambient temperature of control panel: 30 °CIf there are other instruments that generate heat in the controlpanel other than SSRs, additional ventilation will be required.J-44Solid State Relays (Single-phase) G3PBWiring• When using crimp terminals, refer to the terminal clearances shownbelow.Output Terminal Section(Single-phase Models)15-A and25-A ModelsInput Terminal Section35-A and45-A Models107.01312.41012.9M4 (15 A, 25 A)M5 (35 A, 45 A)M3.5• Make sure that all lead wires are appropriate for the current.• Output terminals are charged even when the Relay is turned OFF.Touching the terminals may result in electric shock.
To isolate theRelay from the power supply, install an appropriate circuit breakerbetween the power supply and the Relay.Be sure to turn OFF the power supply before wiring the Relay.Tightening Torque• Refer to the following and be sure to tighten each screw of theRelay to the specified torque in order to prevent the Relay frommalfunctioning.Screw terminaldiameterTightening torqueInput terminalM3.50.8 N·mOutput terminalM41.2 N·mM52.0 N·mSSRItemSolid State Relays (Single-phase)G3PBJ-45J-46Solid State Relays (Single-phase) G3PBSolid State Contactors (Three-phase)G3PBSpace and working time saved with new heatsink construction.
Series now includes480-VAC models to allow use in a greaterrange of applications.• A comprehensive lineup that now includes 480-VAC models.• Slim design with 3-phase output and built-in heat sinks.• New heat sink construction with smaller mounting section.• DIN track mounting supported as standard. (Screw mounting isalso possible.)• Certified by UL, CSA, and VDE.Model Number Structure■ Model Number LegendG3PB-@@@-@@-@12 3 45 67SSR1. Basic Model NameG3PB:Solid State Relay2. Rated Load Power Supply Voltage2:200 VAC5:480 VAC3. Rated Load Current15:15 A25:25 A35:35 A45:45 A4.
Terminal TypeB:Screw terminals5. Single-phase/3-phase and Number of Elements for 3-phase2:3-phase, 2-element models3:3-phase, 3-element models6. 3-phase TypeN:DIN track mounting and built-in heat sink7. CertificationVD:Certified by UL, CSA, and VDESolid State Contactors (Three-phase)G3PBJ-47Ordering Information■ List of Models (Built-in Heat Sinks)Applicablephase3Main circuit voltage100 to 240 VACZero crossfunctionYesApplicable heater capacity (withClass-1 AC resistive load)5.1 kW max. (15 A)8.6 kW max. (25 A)12.1 kW max. (35 A)200 to 480 VACModel3G3PB-215B-3N-VD2G3PB-215B-2N-VD3G3PB-225B-3N-VD2G3PB-225B-2N-VD3G3PB-235B-3N-VD2G3PB-235B-2N-VD15.5 kW max. (45 A)3G3PB-245B-3N-VD2G3PB-245B-2N-VD12.5 kW max. (15 A)3G3PB-515B-3N-VD2G3PB-515B-2N-VD20.7 kW max.
(25 A)3G3PB-525B-3N-VD2G3PB-525B-2N-VD29.0 kW max. (35 A)3G3PB-535B-3N-VD2G3PB-535B-2N-VD37.4 kW max. (45 A)3G3PB-545B-3N-VD2G3PB-545B-2N-VDNote: When ordering, specify the rated input voltage.J-48Number ofpolesSolid State Contactors (Three-phase) G3PBSpecifications■ Ratings (at an Ambient Temperature of 25°C)Operating Circuit (Common)ItemCommonRated voltage12 to 24 VDCOperating voltage range9.6 to 30 VDCRated input current (Impedance)10 mA max. (at 24 VDC)Must operate voltage9.6 VDC max.Must release voltage1 VDC min.Insulation methodPhototriac couplerOperation indicatorYellow LEDMain Circuit of Models with Built-in Heat SinksItemG3PB215B3N-VDG3PB215B2N-VDG3PB225B3N-VDG3PB225B2N-VDG3PB235B3N-VDRated load voltage100 to 240 VACLoad voltage range75 to 264 VACApplicable load current(See note.)0.2 to 15 A0.2 to 25 A0.5 to 35 AInrush current resistance(peak value)150 A(60 Hz, 1 cycle)220 A(60 Hz, 1 cycle)440 A(60 Hz, 1 cycle)Permissible I2t(half 60-Hz wave)260 A2s2,660 A2s2,660 A2sItemG3PB515B3N-VDRated load voltage200 to 480 VACLoad voltage range180 to 528 VACApplicable load current(See note.)0.5 to 15 AInrush current resistance(peak value)220 A(60 Hz, 1 cycle)Permissible I2t(half 60-Hz wave)260 A2sG3PB515B2N-VDG3PB525B3N-VD0.5 to 25 AG3PB525B2N-VDG3PB535B3N-VD0.5 to 35 AG3PB235B2N-VDG3PB245B3N-VDG3PB245B2N-VD0.5 to 45 AG3PB535B2N-VDG3PB545B3N-VDG3PB545B2N-VD0.5 to 45 A440 A(60 Hz, 1 cycle)1,040 A2s1,040 A2sSSRNote: Applicable load current varies depending on the ambient temperature.
Характеристики
Тип файла PDF
PDF-формат наиболее широко используется для просмотра любого типа файлов на любом устройстве. В него можно сохранить документ, таблицы, презентацию, текст, чертежи, вычисления, графики и всё остальное, что можно показать на экране любого устройства. Именно его лучше всего использовать для печати.
Например, если Вам нужно распечатать чертёж из автокада, Вы сохраните чертёж на флешку, но будет ли автокад в пункте печати? А если будет, то нужная версия с нужными библиотеками? Именно для этого и нужен формат PDF - в нём точно будет показано верно вне зависимости от того, в какой программе создали PDF-файл и есть ли нужная программа для его просмотра.